6 final main board checks – E-Mon E20-6003200J-G-KIT User Manual

Page 15

Advertising
background image

GREEN CLASS METER

15

62-0415-01

Verify each current sensor by running at least 1% of the full scale rated current through

the conductor being monitored by each phase. (e.g. 2 amp load required for each

phase to perform sensor diagnostic procedures.)

- Verify that the current sensor white and black conductors are installed in the correct

header positions.

- Verify the current sensors are installed in the correct direction on the conductor being

monitored.

-Verify that the current sensor plugs are terminated in the correct header on the Main

Power Board.

If the error messages still haven’t been cleared, measure the AC voltage inputs across

the plug terminals of each current sensor, individually. Set the AC voltmeter to the 20

Volt scale. If a reading of zero volts is indicated on the voltmeter, check for an open

circuit. An open connection could exist at the plug terminals or at a splicing junction.

Also verify a tight connection exists between the core halves.

If error message is still appearing, contact E-Mon technical support at (800) 334- 3666

for further assistance.

4.6 Final Main Board Checks

Once the phase error has been corrected, the Display LCD “Check Sensor” error

should extinguish and the Main Power Board LED should extinguish.