1 phasing of line voltage – E-Mon E-D5-600800-S*SPL3-V3KIT3 User Manual

Page 19

Advertising
background image

DIN-MON™ SMART METER

19

62-0442—04

4.4.1 Phasing of Line Voltage

The 3-phase AC power input must be in proper phase sequence. If the sequence is

incorrect or a phase is missing, there will be a message on the meter’s display: “PH

Seq Err” or “PH Loss x” where ‘x’ is the missing phase. (Refer to the section on Line

Voltage Diagnostics if this message is present.) When the line voltage is connected

correctly, the error message will not be present.

Wait for the meter display to scroll to the voltage display. Verify that the meter reads

correct voltages on all phases.

Once the meter displays the correct line voltages and there are no error messages,

you are ready to connect the current sensors to the meter. Before continuing with the

installation, verify that the six screens display as follows:

Screen 1 (kWh):

Should read 0.0 kWh.

Screen 2 (kW Peak Demand):

kW peak should read 0.0 kW. There will not be a

date/time stamp yet.

Screen 3 (Load/Date and Time): Should read 0.0 kW load.

Screen 4 (Amps per Phase):

There should be 0.0 on all three phases.

Screen 5 (AC Volts, L-N):

Screen 6 (AC Volts, L-L):

Screen 7 (Power Factor):

There should be 0.0 PF on all three phases.

NOTE: The meter kWh and/or kW peak demand readings can be reset later.