4.5.1 Installing Split-Core Current Sensor Assembly

1. Each phase being monitored will require one split-core current sensor assembly.

Open the current sensor assembly by lifting the top off the sensor.

Fig. 14. Typical Split Core Current Sensor.

2. Reassemble the current sensor assembly around the conductor(s) to be moni-

tored. Ensure the current sensor side marked “This Side Toward Source” is fac-

ing the source side of the metered conductor.

3. Run the Black and White wires from the current sensors to the meter and install

them according to the standard installation diagram.

Fig. 15. Split Current Sensor Dimensions.

P/N

AMPS

A

B

C

D

E

NOTE

50082281-006

100

2.00

2.10

0.60

0.75

0.75

50082281-008

200

3.25

3.35

1.00

1.25

1.25

50082281-010

400

3.25

3.35

1.00

1.25

1.25

50082281-012

800

4.75

5.00

1.20

2.00

2.00

M35137

SOURCE

LOAD

M35102

E

B

A

D

C