LONWORKS SPECIFICATIONS

1. Supports up to 64 Devices / Nodes on a single network segment.

2. Supports 78 kbps bit rate.

3. TP/FT-10 accommodates Bus, Star, Loop, or combinations of topologies.

4. Bus Topology Specifications (Doubly Terminated):

a. MAX Bus Length: 1,000 meters (3,280 Feet).

b. MAX Stub Length: 3 meters (10 Feet).

5. Free Topology Specifications (Single Terminated):

a. MAX Device to Device distance 250 meters (820 Feet).

b. MAX Total Wire Length 450 meters (1476 Feet).

6. Required Termination:

a. Bus Topology: (2) Terminators, ECHELON Model Number 44100R or equiv-

alent.

b. Free Topology: (1) Terminator, ECHELON Model Number 44100R or equiva-

lent.

Fig. 27. LonWorks Bus Topology.

Fig. 28. LonWorks Free Topology.

EMS OR CONTROL UNIT

NETWORK

ADAPTOR

M35117

LONWORKS NETWORK

TERMINATOR

TERMINATOR

MAXIMUM STUB

LENGTH: 10 FEET

MAXIMUM BUS

LENGTH: 3280 FEET

M35118

TERMINATOR

EMS OR CONTROL UNIT

MAXIMUM TOTAL CABLE

LENGTH: 1476 FT.

MAXIMUM DISTANCE

BETWEEN DEVICES

820 FT.

LONWORKS NETWORK

NETWORK

ADAPTOR