TESTING THE SYSTEM

Following installation, test the system as follows :-

First ensure that the system is running and has been allowed time to calibrate (50 seconds after power-
up or reset).

Fire Alarm

Place the striped end of the test filter over the Receiver lens.

A Fire Alarm shall be indicated in approx 10 to 12 seconds.


Fault Alarm

Place a complete blockage (example: a hand) over the Receiver lens. Ensure that the lens is

fully covered.

A Fault Alarm shall be indicated in approx 4 to 6 seconds.