Fire Fighting Enterprises FIRERAY 5000 4-Head (Legacy) User Manual

General information, En quick start guide, Wiring diagrams

Advertising
background image

1. General Information

• Check the beam spacing against

local regulations

• Position beam as high as possible,

but with a minimum distance of 0.5m

from Detector to ceiling

• Mount Detector and Reflector directly

opposite each other

• Do NOT position Detector where

personnel or objects can enter the

beam path

• Do NOT position 2 Detectors facing

each other

• LED indicator must face downward

18—50m = 1

50—100m = 4

8—18m = 1

Use Short

Range Mask

50cm

8-100m

50cm

Ensure clear line of

sight from Detector

to Reflector

Mount on solid surfaces (structural wall or

girder)

50cm

50cm

8-100m

Wiring for all other System Controllers (where more than one System

Controller is on one zone)

(Not to be used for UL region installations. Please refer to supplied CD for

UL region installation multiple-System Controller wiring)

Wiring for a single System Controller or last System

Controller on one zone

ZONE -

ZONE +

SUPPLY -

SUPPLY +

EARTH/SCREEN

Components not supplied (Check Fire Control Panel

manufacturer for values):

• Fire Resistor (Some Zone and Switch Interface Modules

do not need a Fire Resistor - replace Resistor with a

short circuit.)

• Detector Continuity Diode

• End Of Line (‘EOL’) component

• Check operation of Fire and Fault connection on Fire

Panel

• ALWAYS use a separate screened 2-core cable for

each detector head

• CAUTION: For system monitoring – Do not use

looped wire under any terminals. Break wire run to

provide monitoring of connections

Apply a

voltage of

5V to 40V to

‘Ext Reset’

contact for

at least 2

seconds to

clear a

Latched

Fire

condition

DET 1

DET 2

DET 3

DET 1

DET 2

DET 3

DET 4

14V - 28V DC

DET 4

14V - 28V DC

FIRE

ConA

1

2

3

N/O

Fire

Resistor

Fire

Resistor

Ext

Reset

Ext

Reset

EOL

COM N/C

N/O COM N/C

FAULT

ConB

1

2

3

FIRE

ConA

1

2

3

N/O COM N/C

N/O COM N/C

FAULT

ConB

1

2

3

EN

QUICK START GUIDE

Motorised Infrared

Optical Beam

Smoke Detector

2. Wiring Diagrams

Document Number: 0044-033-02-EN

When ‘Set’ is displayed press

When ‘S-00’ is displayed, cover the Reflector with a non-

reflective material and leave covered, then press

When ‘S-01’ is displayed, uncover the Reflector and leave

uncovered, then press

Repeat Steps 8 to 12 for any other Detectors found during

the ‘Find’ process

12. ‘Set’ 0/100 (Calibrate)

13. System is Aligned

It is recommended to set the system back to ‘Lo A’ mode

Green LED on Detector will flash every 10 seconds, and

Signal Strength should be between 99% and 101%

Default values: 35% Fire Threshold, 10 second delay to

Fire and Fault, Non-Latching mode

Refer to User Guide page 13-14 to change settings and

for Fire and Fault Test

14. Check Alignment Status Displays

A commissioned system

will display:

When Detectors have

been found but the

selected Detector is not

aligned the system will

display:

When a Detector is

connected but not

‘Found’ the system will

display:

European Approval Information

Complies with EN54-12 for sensitivity levels between 25%

and 35% with a maximum delay to fire of 20 seconds.

UL Approval Information

UL File Number: S3417

Distance between

Detector and Reflector

Fire Threshold

Range

8

10m (26.2

32.8ft)

10

18%

10

15m (32.8

49.2ft)

15

25%

15

22m (49.2

72.2ft)

15

35%

22

40m (72.2

131.2ft)

25

50%

40

60m (131.2

196.8ft)

35

50%

60

100m (196.8

328.1ft)

50%

All installations should comply with NFPA72

Approvals Information

Troubleshooting

E-01

Detector Not Found
System Controller could not find

Detector. Also displayed during

power up

• Wait 45 seconds for system to power up

• Check wiring between System Controller and

Detector (Voltage to Detector should be 11—13V)

E-02

Detector is connected but not

‘Found’

• Follow ‘Find’ process and align if necessary

E-08

Compensation Level Not Zero
Compensation must equal zero

when ‘Set’ is selected

• Re-align Detector using Auto-Align

E-09

Signal Strength Out of Range
Signal Strength is too low or too

high after Auto-Align

• Ensure correct distance has been set

• Ensure correct Reflector type has been used

• Ensure clear line of sight to Reflector

• Re-align Detector using LASER and Auto-Align

E-10

Reflector Not Found
Detector could not align with

Reflector

• Ensure correct distance has been set

• Ensure correct Reflector type has been used

• Ensure clear line of sight to Reflector

• Re-align Detector using LASER and Auto-Align

E-11

Auto-Align Failed

• Ensure correct distance between Reflector and

roof structures

• Ensure clear line of sight to Reflector

• Re-align Detector using Auto-Align

E-12

Cannot Zero During ‘S-00’ in

‘Set’
The Reflector was not covered or

the Detector was not aligned

onto the Reflector

• Ensure Reflector was completely covered with a

non-reflective material

• Re-align Detector using Auto-Align

E-13

No Signal During ‘S-01’ in ‘Set’
The Reflector was not uncovered

during ‘S-01’

• Ensure Reflector was uncovered when ‘S-01’ was

selected

E-14

‘Centre’ Stage of Alignment

Failed
Detector has aligned on some-

thing other than the Reflector

• Ensure clear line of sight from Detector to

Reflector for a radius of 0.5m

ENGLISH FINAL - A3 QSG:Layout 1 27/01/2010 09:56 Page 1