Fire Fighting Enterprises FIRERAY 5000 4-Head (Legacy) User Manual

Page 3

Advertising
background image

All functions can be performed in ‘Lo A’

mode (default) (10, 12, 14 or 16 mA

for 1, 2 ,3 or 4 Detectors found)

The system will default to ‘Lo A’ mode

when power is applied

Select ‘Hi A’ (50mA) to enable faster

beam movement during Auto-Align,

Hand Align and Laser Targeting

After installation, set the system back

to ‘Lo A’

7. Select Power Mode

1. Use

to move

between icons in the
Engineering Menu, to
highlight the icon shown

3. Use

to move to

required item

2. Press

to select

4. Use

to

change selection

5. Press

to accept

Press

to cancel

Select 8-50m (default) or 100m

It is possible to set the range of

each invidual Detector

9. Select Distance

between Detector

and Reflector

Select Detector to be accessed

All Detectors need to be aligned

separately

Steps 9 to 12 explain how to

align individual Detectors

8. Select Detector

1

2

3

4

The system will signal Fault while in this mode

The LASER is used to align the Detector with the Reflector.

It is an approximate alignment tool only. After Auto-Align

the LASER will not necessarily be pointing on the Reflector

• Use

to move the LASER as close to the

Reflector as possible

• One press of an arrow key results in one movement of

the Detector head

• Press

or

to turn off the LASER and return to the

Settings menu

• Refer to User Guide page 20 for troubleshooting if

LASER is not visible

LASER RADIATION - AVOID

DIRECT EYE EXPOSURE
POWER OUTPUT < 5mW
CLASS IIIa LASER
Wavelength 630 - 680 nm

DANGER

10. LASER Targeting

• Select ‘Auto’ to automatically

align the infrared beam

• Signal Strength will be shown

during Alignment

• If the LASER is turned on it

will not necessarily be

pointing on the Reflector after

‘Auto’ is run - this is normal

11. ‘Auto’ Alignment

LoA: 7 minutes

HiA: 4 minutes

5. Enter Pass Code to

Access Engineering Menu

4. Apply power

‘E-02’ at this stage is

normal

2 seconds

15 seconds

40 seconds

Default Pass Code: 1 2 3 4

Change digit

Move between digits

Accept

One System Controller can be used to

control and monitor up to four Detector

heads.The ‘#’ symbol in this guide is

used to represent the number of the

Detector currently selected (1, 2, 3 or 4).

LED indicator must face downward

3. Fitting the Product

An incorrect Pass Code will return the

display to the Pass Code entry screen

Three incorrect attempts will lock access

for three minutes

6. Find Detectors

60 seconds

Press tick to enable ‘Found’

Detectors

Any unused Detector channels

are switched off

Press

to re-scan if number is

incorrect

This will be

the number of

Detectors

found

‘Find’ is automatically displayed

the first time this process is run.

‘Find’ can also be accessed in the

System Controller settings menu

Press

for Pass Code screen:

ENGLISH FINAL - A3 QSG:Layout 1 27/01/2010 09:57 Page 2