Fire Fighting Enterprises FIRERAY 2000 (Legacy) User Manual

Page 8

Advertising
background image

Fireray 2000 Installation Guide 22318.00.R 25.08.05

8

Technical Specifications

Data

Operating

Temperature

-20

°C to +55°C

Operating Voltage

11.5 to 28 Volts DC

Transmitter

Current

< 1.6 – 5.6mA

Control Unit (includes Receiver) Quiescent Current

< 8.5mA

Control Unit (includes Receiver) Alarm Current

< 16.5mA

Control Unit (includes Receiver) Fault Current

< 16.5mA

Operating Range (distance between Transmitter and Receiver) 10 to 100 metres

Receiver tolerance to beam misalignment

± 4°

Transmitter tolerance to beam misalignment

± 1°

Fire alarm thresholds

1.25dB (25%), 1.87dB (35%), 3dB (50%)

Optical wavelength

880 nm (Infra red)

Control Unit max dimensions

215mm x 265mm x 88mm

Transmitter and Receiver max dimensions (inc. brackets)

83mm x 115mm x 135mm

Control

Unit

weight

1060

gms

Transmitter and Receiver weight (inc. brackets)

650 gms

Relay Contacts

2A 30 Volts DC resistive

Fireray 2000 Selectable Options

SWITCH OPEN

CLOSED

ALARM LATCH

Fire relay will automatically reset

§

Fire relay will not auto reset (latch)

COMP

For BS5839 part 5 leave open.

§

At the last AGC stage the Fireray will signal a fault,
but in the event of any further signal loss reducing
the signal to the selected threshold level, a fire alarm
will be signalled

At the last AGC stage the Fireray
will signal a fault, the fire relay will
be inhibited

25%

25% Alarm sensitivity selected

35%

35% Alarm sensitivity selected

§

50%

50% Alarm sensitivity selected

NOTE: Select ONE Alarm sensitivity level only.

§ Factory Default Settings.

Application Notes

For full compliance with BS5839 part 5, use the 25% and 35% thresholds. The 50% threshold is only
recommended for hostile environments.

Service Notes

Control Unit contains ESD sensitive devices; appropriate care must be taken when handling internal
components.

Parts List

1 Transmitter (clear lens).

1 Receiver (dark lens).

1 Control Unit.

2 Right angle brackets.

4 Bolts and washers.

1 Test Filter.

Fig 7

FIRE FIGHTING ENTERPRISES LIMITED

9 Hunting Gate, Wilbury Way, Hitchin

Hertfordshire SG4 0TJ England

Tel: +44 (0) 845 4024242 Fax: +44 (0) 845 4024201  Email: [email protected]

www.ffeuk.com

Advertising