System design, Service & repairs – Fire Fighting Enterprises Talentum IR3 Flame Detector User Manual

Page 6

Advertising
background image

6



























Flameproof Flame Detector
(Stainless Steel Housing)
Fig. 2



























Technical Data


Mechanical
Housing Material:

See figure 2

316 Stainless Steel

Housing Colour:

Natural

Housing
Dimension:

(Excluding Mounts)

Height = 150mm
Width = 146mm
Depth = 137mm

Cable Gland
Entries:


3 X 20mm - typical


Electrical
Supply In:

Voltage

Current

Polarity sensitive

Terminals 1(+) & 2(-)

14 to 30Vdc
2 to 28mA

See data

sheet for detail

Optional Input:

Voltage

Current

Polarity sensitive

Terminals 3(+) & 4(-)

14 to 30Vdc
40µA

typ. @

24V IN

Power Up Time: 2 seconds

Relays
Contact Ratings:

Voltage

Current

Power

Resistive Loads Only

Terminals 5 to 8

30Vdc. Max.
1 Amp. Max.
30W Max.


Environmental

ATEX
Approval Category



II 2 G D

CENELEC / IEC
Marking

Ex d IIC T4 Gb
Ex tb IIIC T135°C Db

(Zone 1, 21, 2 & 22)

Ambient Temperature

Range:

Also check

detector data sheet.

Tamb -40°C to +125°C

Apparatus
Certificate
Numbers

Baseefa08ATEX0270

IECEx BAS08.0073

IP Rating

IP66



7

System Design


Engineers familiar with codes of practice for
hazardous area systems should only
undertake the design of an flameproof fire
detection system. In Europe the standard is
EN 60079-0 (formally EN 50014), Electrical
apparatus for potentially explosive
atmospheres – General requirements.

The fire detector performance is the same as
the standard none flameproof counterparts.
Performance information given in standard
product guides is therefore applicable to the
flameproof range.


The Baseefa certification of the flameproof
device enclosure covers their characteristics
as components of a flameproof system. This
indicates that the flame detectors can be
used with a margin of safety in such
systems.








Service & Repairs

1.

Frequent inspection should be made. A schedule for the maintenance check should be
determined by the environment and frequency of use but should be regular enough to
ensure the detector continues to operate in the designed manner. It is recommended that
it should be at least once a year.


2.

External surfaces of the enclosure should be periodically cleaned to ensure dust deposits
are not allowed to accumulate.

3.

Check flamepath/threads on enclosure body and lid for signs of corrosion. If badly pitted,
replace component.


4. All components that are replaced must be in accordance with the manufactures

specification. Failure to use such components may invalidate the certication/approval on
the enclosure and may make the enclosure dangerous.

5.

After inspection and maintenance have been carried out, items 3 & 4 of the installation
instructions should be adhered to when resealing the enclosure.


Servicing of the fire protection system should be carried out as recommended by the local regulation
in force.