FIREPOWER MXL-IQ User Manual

Page 7

Advertising
background image

CCU/M and RDM-MXL

CCU/M Alphanumeric Pager Interface

The CCU/M is a ancillary module that connects to the

PIM-1 to transmit MXL-IQ status information in text

message format to an alphanumeric pocket pager. The

CCU/M can be connected to an existing phone line and

can dial out to a pager using its onboard modem to

transmit information via a paging service. The CCU/M

can also connect directly to an existing on-site paging

system. Through programming the CCU/M can send

different types of events to different pagers. Up to 8

different messages can be sent to pagers directly from

the CCU/M. Alarms, Troubles, Supervisory, Security,

Arm/Disarm, Status Points, Audible Status, and Reset

can be directed to all or only certain alphanumeric

pocket pagers.

MSE-3L MXL-IQ Enclosure/Door

The MSE-3L is a sheetmetal backbox for the MXL-IQ

system. The MSE-3L supports mounting for the SMB-2,

MPS-6, MPS-12, MPS-12-220, MPS-12-240, MKB-4 and

either one MOM-2 or one MOM-4 cardcage. The MSE-3L

dimensions are 27

1

/

16

”H x 21

1

/

8

”W x 6”D. The IQ-DFL

plate (500-695436) is also available for use with the

MSE-3L to provide full deadfront construction. The MET-

3L (500-695437) flush trim mounting kit is also available

for use with the MSE-3L enclosure. The MET-3L pro-

vides an optional 1” trim mounting ring around the

MSE-3L. The MSE-3L enclosure also has provision for

mounting a PSR-1 remote power supply, for use in place

of the SMB-2 for MXL and MXLV applications. When the

PSR-1 is mounted in the MSE-3L enclosure the IQ-

BLANK (500-695438) blank plate is available to cover the

cutout in the MSE-3L door. Other versions of the MSE-

3L include; MSE-3LR - Red version of the MSE-3L and the

MET-3LR - Red version of the MET-3L trim ring kit.

MSE-3L

14 in

The RDM-MXL in combination with the RDM-PC pro-

vides the ability to call up an MXL, MXL-IQ or MXLV

system to check on the system status. The RDM-PC

connects a remote computer to the MXL equipped wit

the RDM-MXL. The RDM-PC initiates a call to the MXL’s

RDM-MXL module. The RDM-MXL answers the call.

The RDM-PC identifies itself with the login name. As a

built-in security measure, when the login name is

recognized by the RDM-MXL, it then hangs up and

initiates a call back to verify the login and password.

Once the login and password is verified, the operator is

on-line with the MXL. The operator can list system

status, alarms, troubles, supervisories, and/or security

events!

REP-1

The REP-1 is an optional MXL module that extends

the distance of the MXL’s RS-485 network. The REP-1

provides the ability to support various wiring configu-

rations, including series and star configurations. The

REP-1 provides the ability to support NFPA Style 4

or Style 7 network communications wiring. The REP-1

can be used to provided network wiring between

MXL panels or MXLR panels. The REP-1 is a one -half

slot card that plugs into a MOM-4 or MOM-2

cardcage. The REP-1 allows MXL network distances

to be expanded to allow greater application flexibility.

The REP-1 is an RS-485 repeater module capable of

being configured as one Style 7 or two Style 4 net-

work communication lines.

RDM-MXL, RDM-PC

REP-1

27.06 in

Advertising