General Technologies FF310 Fault Finder for Electrical Wiring Open / Short Circuit User Manual

Page 4

Advertising
background image

Page 5

Page 4

6.10 The short circuit is located in the area where the audio/visual signal stops or

changes significantly.

6.11 When the test is completed, switch off the transmitter unit pressing the On/Off button

and disconnect from circuit.

Note: The closer the tracer probe is to the wire carrying the signal, the faster the

beeping and the flashing will be. Some times it will prove advantageous to reduce

the sensitivity level to pint point more accurately the faulty area.

7 - Wire tracing

Wire tracing hook up and procedures are essentially the same as for locating short circuits.

The transmitter sees the load (light, accessory, etc.) as the short circuit or connection

to ground. For wire tracing simply follow the wire with positive (beeping and flashing)

audio/visual indicator’s feedback on the tracer from source to load.
For step by step directions please refer to point

6– Locating Short Circuits, for some

hints and specific differences refer to the notes below:
The type and size of load connected to the circuit (impedance or resistance to ground)

determines the amount of current allowed to flow in the circuit. Small loads (low Wattage

lamps, electronic systems, etc.) will reduce the range of the tracer accordingly. In cases

where the full range of the tracer is required to follow the wire, it may prove advantageous

to use one of the two methods described below:

Tracing wires downstream (from supply to load): replacing the load for a full short

circuit allows the FF310 to work at its maximum capabilities. Before proceeding

remove all electrical power from the circuit, connect the FF310T in series with the

wire to trace, short circuit the load to ground (refer to

Hook Up Reference Chart

Fig.2 and 3), then reconnect power and follow instructions in section

6 – Locating

Short Circuits.

Tracing wires upstream (from load to supply): If more convenient, wires can also be

traced the other way around, by replacing the load with the FF310T (Fig. 4 of Hook

Up reference chart). To do this, first remove power from the circuit, disconnect load

and connect the FF310T in its place. Apply power to the circuit and follow instructions

in section

6 – Locating Short Circuits.

8 – Locating Current Leaks

Hook up and procedures for locating current leaks are essentially the same as for

locating short circuits. The transmitter sees the leak as a weak short circuit or

connection to ground. For locating a current leak simply follow the wire with positive

(beeping and flashing) audio/visual indicator’s feedback on the tracer, from source to leak

location (short circuit).
For step by step directions please refer to point

6 – Locating Short Circuits, for some

hints and specific differences refer to the notes below:
Current leak notes:

The type and size of the leak in the circuit (impedance or resistance to ground) de-

termines the amount of current flowing in the circuit. Small leaks (i.e. low current) will

reduce the range of the tracer accordingly. In all cases the FF310R’s probe should be

positioned as close as possible to the wires, in order to maximize the signal captured

by the tracer, and set to a higher sensitivity level . For hook up refer to the

Hook Up

Reference Chart Fig. 2 and 3 in Page 6.

9 - Locating Open Circuits

Refer to the Hook Up Reference Chart in Page 6.
9.1 Observe the limits and safety precautions at all times (refer to the beginning of

this handbook)

9.2 Connect the FF310T (transmitter) in series with the open ended wire, making sure

one of the unit’s clips is connected to the circuit’s positive supply or ground . A fuse

socket ( with the fuse removed), a connector, etc., provides a convenient hook-up

as shown in Fig. 2, 3, 4 and 5 of the

Hook Up Reference Chart.

9.3 Make sure that the clips are firmly attached to their connection points, and switch

the transmitter on by pressing the On/Off button. Observe if the Green LED on

the FF310T starts flashing. In the case of having connected the unit to any place

other than the fuse socket, check that the circuit’s fuse is installed and in working

condition (not open). If necessary replace with a new fuse with same rating.

9.4 Switch the FF310R (tracer) on, and check if green LED turns ON and set if

necessary the sensitivity level to “

LOW”.

9.5 Slowly sweep the wire with the FF310R, ensuring the tracer’s probe is perpendicular

to and above or below the wire being traced and as close as possible to it .

9.6 Follow the wire or check it at different points, starting from the transmitter and

moving towards the load (accessory, light, etc.), observing the positioning of the

probe as indicated above. Continue this procedure while the audio signal (beep-

ing sound) and visual signal (flashing green LED light) indicates the integrity of

the circuit. If beeping and flashing slows or stops, it indicates that the probe is

either moving away from the wire or it has passed beyond the open, break or bad

connection in the circuit.

9.7 If difficult or impossible to get the FF310R Tracer to pick-up any signal, then adjust

the sensitivity to”

HIGH” and repeat again step 9.6.

9.8 Double check by positioning the probe before and after the suspected place. If

the open circuit point has been found, the audio/visual indicators will show circuit

integrity on one side, and not on the other.

9.9 At this point, where the audio/visual signal stops, you have found the open circuit.
9.10 When the test is completed, switch off the FF310T (transmitter) unit pressing the

On/Off button and disconnect from circuit. You may also switch OFF the FF310R

(tracer) by pressing the On/Off button on the unit. However to conserve power, the

FF310R will automatically turn off after 3 minutes of not being used.

Note: The closer the tracer probe is to the wire carrying the signal, the faster the beeping

and the flashing will be.

10 - Wire identification

Refer to the

Hook Up Reference Chart in Page 6.

Wiring can be identified by following the hook up and procedures for locating short circuits

or open circuits, depending on the particular configuration of the circuit.

For identifying wires with load connected: Connect transmitter as described

in section ‘

6- Locating Short Circuits’ to the circuit to be identified, then

proceed to scan all suspected wiring with the FF310R’s probe until the flashing and

beeping is at its maximum. In the case of tightly packed wires ( bundles, conduits, etc.),

it may be necessary to spread these apart to facilitate the identification process of

a particular wire.

Advertising