9060 Cascade Low Voltage Controller - Operation

37

CP-13-02.2

Adjusting Presets

To adjust one of the preset setpoints, ensure
the applicator is off in LOCAL mode and select
the desired setpoint by pressing the corre-
sponding setpoint button. The setpoint can
then be adjusted between 20 kV and full kV
using the + and - buttons on the front panel of
the 9060 Controller shown in Figure 31. Single
pushes of the + or - buttons will increment or
decrement the currently selected preset in units
of 1. When the + or - buttons are held in for
longer than 1 second, the kV display will begin
incrementing or decrementing in units of 5.

Figure 31: kV Adjust/Setpoint Buttons

REMOTE MODE ONLY
OPERATIONS

Tripleset Selection

The tripleset signals are used to select voltage
setpoints (presets) that are used during Local
Mode operation. To select a setpoint, the
tripleset signals must be set to the correspond-
ing binary combination as listed in the Tripleset
Selection Table.

TRIPLESET SIGNAL TIMING:
The minimum hold time for the setpoint selec-
tion signals is 10 ms.

The three setpoints can ONLY be ad-

justed in LOCAL mode.

N O T E

Resetting Faults

During operation, various faults can occur
based upon the operating conditions or if any
problems with the 9060 unit arise. If a fault
occurs, to reset a fault, the trigger signal MUST
be off and then press the Reset Button . This
will clear the fault status and put the unit back
into operation unless a fault condition is still
present. Please refer to the “Fault Description”
portion of the Operation Section of this Service
manual for more information on a specific fault
and how to correct it.

TS1

TS0

Selection

0 (off)

0 (off)

No Change

0 (off)

1 (on)

Preset 1

1 (on)

0 (off)

Preset 2

Tripleset Selection

1 (on)

1 (on)

Preset 3

After the hold time, the simultaneous

signals can be returned to off, but they
must be at the same time to avoid falsely
selecting a different setpoint.

N O T E

The presets can NOT be adjusted in

remote mode. The unit must be in LO-
CAL mode and the preset values must be
adjusted using the front panel.

If adjustable voltage setpoints are

needed, analog kV setpoint signaling is
required.

N O T E

For tripleset to control the kV setpoint,

no analog kV set signal should be active.

!

C A U T I O N

Single Pushes Increment Voltage Down (-) or Up (+)in
Single Increments. Holding Button Increments Voltage
Down (-) or Up (+) in Increments of 5 Kv.

Set Point Select Button

There is a 5 second fault reset delay

timer that inhibits the triggering of high
voltage immediately after a fault reset.

N O T E