Analog output, Relay contact outputs, 9060 cascade low voltage controller - introduction – Ransburg 9060 LV Cascade Controller 80120-XXX User Manual

Page 20

Advertising
background image

9060 Cascade Low Voltage Controller - Introduction

15

CP-13-02.3

Remote Mode Configuration is set to enable
Analog Control. For more information on
how to configure Remote Mode, please see
the Operation section of this service manual.

Analog Setpoint Control

In analog setpoint control, the unit will output
voltage from the minimum voltage of 20kV (2V
or 4mA) up to the maximum kV allowed for the
specific gun configuration. Depending on the
analog control signal being used, the signal
can be adjusted from 0-10V (or 0-20mA) which
are mapped directly to 0-100kV. For example,
8 VDC (or 16mA) will produce an 80kV set-
point if it is within the maximum voltage of the
applicator. After the applicator’s maximum
setpoint is reached, further increases in analog
signal will NOT result in a setpoint increase.
The lower part of the range below 2V (4mA)
will set the cascade to output 0kV allowing for
the cascade to remain energized while output-
ting no voltage. The analog control signal
value can be adjusted at any time during
operation of the unit as long as the unit is in
remote mode, regardless of the state of the HV
trigger signal.

Analog Voltage Signal

The analog voltage signal (TB3-3) is an input
control signal that adjusts the KV setpoint
scaled relative to the voltage signal applied.
The allowable range for the voltage control
signal is 0-10V mapped directly to a setpoint
range of 0-100kV, or (1V per 10kV). When the
analog signal is less than 2V, the KV setpoint
is set to 0kV and the cascade outputs no
voltage.

Analog Current Signal

The analog current signal (TB3-2) is an input

control signal that adjusts the KV setpoint
scaled relative to the current signal applied.
The allowable range for the current control
signal is 0-20mA mapped directly to a setpoint
range of 0-100kV, or (2mA per 10kV). When
the analog signal is less than 4mA, the KV
setpoint is set to 0kV and the cascade outputs
no voltage.

Analog Common Signal

The analog common signal (TB3-4) is the
connection for the common reference (-) of the
analog signal source. It is used as the com-
mon for both the voltage and current signal.

Analog Output

The 9060 Cascade Low Voltage Controller
provides a single analog output signal that can
be used for monitoring the current output. This
output can be used for simple monitoring or it
can be used by the control system to allow for
closed loop analog setpoint adjustment.

Analog Current Signal

The analog current output signal (TB3-5) is a 0
-10V signal scaled to represent a 0-200µA
current output range (20µA/1V or approximate-
ly 1µA/50mV). The current signal provided
can easily be integrated with common systems
like PLCs.

Relay Contact Outputs

The relay contact outputs are the HV On and
Fault outputs that were previously described in
the Signal Interface - Local Mode section.
Their descriptions are duplicated here for
completeness.


Although the allowable range for the

analog current signal does include 0mA-
3mA, it will normally be listed as 4-20mA
as the 0-3mA portion of the range is insuf-
ficient to override KV setpoint control.

N O T E

DO NOT attempt to use both analog

voltage and analog current at the same
time. The analog inputs are mutually ex-
clusive

. Using both inputs simultaneous-

ly will damage the input circuit. Only one
analog input, current or voltage, can be
used at time to control the setpoint value.

!

W A R N I N G

Advertising