Analog inputs, 9060 cascade low voltage controller - introduction, Local/remote mode signal – Ransburg 9060 LV Cascade Controller 80120-XXX User Manual

Page 19: Reset signal, Remote trigger signal, Tripleset signals (setpoint 0 and setpoint 1), Triple set combinations

Advertising
background image

9060 Cascade Low Voltage Controller - Introduction

CP-13-02.3

14

or all sinking inputs. For information regard-
ing configuring the inputs, refer to the
“Installation” section of this manual.

Local/Remote Mode Signal

The local/remote mode signal (TB4-4)
indicates to the 9060 Controller whether the
system is currently in LOCAL mode or
REMOTE mode. If the signal is off, the
system will be in LOCAL mode. If the signal
is on, the system will be in REMOTE mode.

Reset Signal

The reset signal (TB4-3) will reset any fault
or overload condition that has occurred. It
will NOT prevent any other existing fault
conditions from re-faulting the system
immediately after resetting. Please refer to
the “Operation” section of this service
manual for fault reset and troubleshooting
information.

Remote Trigger Signal

The remote trigger signal (TB4-5) is used to
indicate to the 9060 Controller to turn on the
high voltage.

Tripleset Signals
(Setpoint 0 and Setpoint 1)

The tripleset signals, Setpoint 0 and Setpoint
1 (TB3-1 and TB4-2), are a pair of signals
that are used to select one of the three
preset voltages that are normally selected
during LOCAL mode operation via the three

preset buttons on the left side of the front
panel. The two signals are used together as
a binary number to select the corresponding
preset value. The selected preset value will
not change unless a different preset value is
input. The binary combinations and their
resulting selection are listed in the Triple Set
Combinations table. These signals can only
be used when the Remote Mode Configura-
tion is set to disable Analog Control. For
more information on how to configure
Remote Mode, please see the Operation
section of this service manual.

Analog Inputs

Two (2) analog input signals, along with an
analog common input, are provided on the
9060 Cascade Low Voltage Controller for
analog control the KV setpoint value. One
signal is provided for analog control using a
voltage signal, the other for a current signal.
The analog inputs are intended for applicator
systems that require either more than 3
presets or an adjustable setpoint voltage.
These signals can only be used when the

Setpoint 1 Setpoint 0

Selection

0 (off)

0 (off)

No Change

0 (off)

1 (on)

Preset 1

1 (on)

0 (off)

Preset 2

Triple Set Combinations

1 (on)

1 (on)

Preset 3

The tripleset signals can be used to se-

lect a preset from the three (3) preset volt-
ages. The preset values can NOT be ad-
justed from REMOTE mode. To adjust
the preset values stored in the 9060, the
unit MUST be in LOCAL mode. If the
voltage setpoint must change between
more than 3 values, one of the analog KV
setpoint signals should be used.

N O T E

Sinking and Sourcing refers to the sig-

nal that is applied to activate an input. If
you are applying a +24 VDC signal to the
input to activate it, you are sourcing. If
you are applying a GROUND signal to the
input, you are sinking.

N O T E

There is a 5 second fault reset delay

timer that inhibits the triggering of high
voltage immediately after a fault reset.

N O T E

Advertising