9060 Cascade Low Voltage Controller - Wiring Configurations

53

CP-13-02.3

Remote Tripleset Point Control (Sourcing Configuration)

The following example configuration uses the following:

Sourcing Configured Digital Inputs (Apply 24VDC to activate the input)

Normally Open (NO) Contact to Activate Reset when unit is Faulted

Normally Open (NO) Contact to Activate HV Trigger to turn on HV Cascade

Normally Open (NO) Contact to Activate remote mode. Turn off to move back to local mode to
allow preset values to be changed

Normally Open (NO) Contacts to Activate Setpoint 0 and Setpoint 1 to select the desired pre-
set value

Figure 46: Remote Tripleset Point Control (Sourcing Configuration)