Unit Description

Air-Radicator Purging

When a refrigerant source has been determined to be pure (at least 98% by weight of

either R-12 or R-134a), the instrument automatically offers the air purging feature to the

user, should there be any air contamination. Continuous monitoring of the venting gas

stream to determine exact air concentrations controls the purging feature. Purging limits

can be set by the user between 2%–9% by weight to tailor the purge to specific needs. The

instrument controls all functions of the purging feature with no intervention by the user

required to complete the procedure. The user can halt or cancel this procedure at any time.

Control of the purge operation is achieved through direct measurements of refrigerant

concentration and is not dependent upon temperature or pressure measurements.

Existing technology in the vehicle air conditioning market typically uses both pressure

and temperature measurements to determine air concentration and to control the

purging procedure. Pressure-temperature technology is susceptible to errors induced by

refrigerant contamination and difficulties in obtaining precise temperature and pressure

measurements. This is due to the inability to account for rapid temperature and pressure

drops of the refrigerant during the purge procedure by temperature-pressure based

equipment or procedures. Temperature-pressure based technology commonly requires

the refrigerant source to come to a temperature-pressure equilibrium before purging can

begin. This process can take as long as eight to 24 hours.

With direct measurement of refrigerant concentrations, there is no need to wait for

a refrigerant source to reach a temperature and pressure equilibrium. Also, rapid

temperature and pressure changes during purging operations do not affect the

measurements.