Securitron DSB_Series User Manual

Page 9

Advertising
background image

PN# 500-22700

Page 8

Rev. F, 03/11

8. ELECTRICAL CONNECTIONS AND WIRING
8.1. DSB WIRING
The DSB is supplied with either a 16-foot [4.88 meter] long cable with traditional wire leads or
an ElectroLynx wiring harness. Either of these wiring devices may be used to connect power to

the main PC board of the DSB. The following figures and table identify the contact numbers,

wire colors and functions assigned for DSB power and DPST relay output:

Figure 10

Traditional Wiring Connector

ElectroLynx Wiring Connector

Connector

Contact

Number

Wire Color

Function

Connector

Contact

Number

Wire Color

Function

1

Red

Positive (+)

1

Black

Common (-)

2

Black

Common (-)

2

Red

Positive (+)

3

Orange

Normally Open #1

3

White

Normally Closed #1

4

Blue

Normally Open #2

4

Green

Normally Closed #2

5

White

Normally Closed #1

5

Orange

Normally Open #1

6

Green

Normally Closed #2

6

Blue

Normally Open #2

7 N/A

Not

assigned

7 N/A

Not

assigned

8

N/A Not

assigned

8

N/A Not

assigned


The male connector of the cable or ElectroLynx wire harness is plugged into the 8-pin female

connector on the main circuit board so that the cable routes directly back into the end mount of

the DSB.

The DSB is operated by a control relay which changes state when the bar is touched. For

additional safety the DSB is a fail safe device. When the DSB receives power, the control relay

automatically energizes the lock. When the bar is touched, it changes state. For releasing a
magnetic lock, the following wiring diagrams (Figures 11 and 12) show typical connections of

the dual sense bar, power supply and a fail safe lock in use on single and double door exits

without an access control unit.

THE WHITE (NC1) WIRE MUST ALWAYS CONNECT TO THE INCOMING (+) POWER WIRE

FOR THE BAR TO OPERATE CORRECTLY.

Figure 11 – Single Door (No Access Control Unit)