APPENDIX B
Wire Gauge Factoring
Remote Power Supply

 The iMXDa/iEXDa requires adequate voltage and current for proper operation.

 Resistance is created by the length and gauge (size) of the wire being used.

 An accurate estimated distance from the power supply to the opening is crucial.

 For optimum operation the correct size gauge wire must be used.

 The devices used operate the best with the least amount of resistance on the source.

 Using the correct gauge wires protects against large voltage and current (load) losses.

 The gauge is determined by the wire distance, voltage and current of all devices.

Determining Wire Gauge

 Follow Example A (12VDC system) and Example B (24VDC system) below.

 Use Table B-1 and Table B-2 to determine the correct wire gauge for the application.

Example A: (an iMXDa used in a 12VDC system)

Devices Used

Amps (12VDC)

Progressive Totals

iMXDa

0.370

0.370

DK-26 Access

0.160

0.530

MK Bypass/Reset

0.020

0.550

Total Current Rounded Up (Table 1)

0.600A


Using Table B-1 (12VDC) Find: - Current Draw .600 Amps

- Wire Distance 200 Feet (One-Way)

Solution: 18 Gauge is indicated for proper installation

Example B: (an iEXDa used in a 24VDC system)







Using Table B-2 (24VDC) Find: - Current Draw .400 Amps

- Wire Distance 200 Feet (One-Way)

Solution: 22 Gauge is indicated for proper installation

TO SOLVE: INTERSECT ROW (Current) and INTERSECTING COLUMN (Wire Distance)

CURRENT WIRE

GAUGE

1.000A 20 18 16 14 14 12 10 10 8

.800A 22 18 18 16 14 12 10 10 8
.600A 22 20 18 18 16 14 14 12 10
.400A 22 22 20 18 18 16 14 14 12
.300A 24 22 22 20 18 18 16 14 14
.200A 24 22 22 22 20 18 18 16 14

50’

[15m]

100’

[30m]

150’

[46m]

200’

[61m]

300’

[91m]

400’

[122m]

500’

[152m]

750’

[229m]

1000’

[305m]

12VDC

WIRE DISTANCE

Table B-1

CURRENT WIRE

GAUGE

Devices Used

24VDC Amps

Progressive Totals

iEXDa

0.270

0.270

TSB Touch Bar

0.025

0.295

DK-11 Access

0.070

0.365

Total Current Rounded Up (Table 2)

0.400A