APPENDIX D
Specific Building Codes
The following general information on code requirements should not be considered definitive. The

information provided represents Securitron’s best understanding of individual codes at the time
of this manual’s most recent revision. Codes, however, may change and are also subject to local
interpretations that may differ from those provided here. Please consider this information as a
preliminary point of reference which should be confirmed or altered in accordance with the
direction given by any local authority having jurisdiction.
The following chart (Table D-1) describes four individual building code requirements in five
areas of function: Nuisance Delay, Release Delay, Post Alarm Relocking, Power Loss and Special
Application Requirements.

FUNCTION

Nuisance

Delay

Release

Delay

Post Alarm

Relocking

Power

Loss

Special

Application

Requirements

NFPA-101

NATIONAL FIRE

PREVENTION

ASSOCIATION

[LIFE SAFETY

CODE]

(2006)

Permitted:

1-3 Seconds

- - - - - - - -

Selectable

Permitted:

15 Seconds

- - - - - - -

Local

Approval

30 Seconds

Relocking

- - - - - - - -

Manual

Means

ONLY

Door

Releases

Upon
Loss

of

Power

Visible Sign

(1" High x 1/8"

Stroke)

- - - - - - - - -

Reading:

"PUSH UNTIL

ALARM SOUNDS"

"DOOR CAN BE

OPENED IN 15 [30]

SECONDS"

IBC

INTERNATIONAL
BUILDING CODE

(2006)

Permitted:

1 Second

- - - - - - - -

Fixed

Permitted:

15 Seconds

- - - - - - -

Local

Approval

30 Seconds

Relocking

- - - - - - - -

Manual

Means

ONLY

Door

Releases

Upon

Loss

of

Power

Visible Sign

(Within 12" of

Releasing Device)

- - - - - - - - -

Reading:

"PUSH UNTIL

ALARM SOUNDS"

"DOOR CAN BE

OPENED IN 15 [30]

SECONDS"

Recognized But

Not Active

BOCA

BUILDING

OFFICIALS CODE

ADMINISTRATORS

(2000)

For

Reference

Only

Permitted:

1 Second

- - - - - - - -

Fixed

Permitted:

15 Seconds

- - - - - - -

Local

Approval

30 Seconds

Special

Relocking

Sequence:
- - - - - - -

Delayed

Relock

30 Second

Post Door

Closure

- - - - - - -

Custom

Times

Available

Door

Releases

Upon
Loss

of

Power

Visible Sign

(Within 12" of

Releasing Device)

- - - - - - - - -

Reading:

"PUSH UNTIL

ALARM SOUNDS"

"DOOR CAN BE

OPENED IN 15 [30]

SECONDS"

NBC

NATIONAL

BUILDING CODE

OF

CANADA

(2005)

Not

Allowed

- - - - - - - -

Fixed

Permitted:

15 Seconds

- - - - - - -

ONLY

Relocking

- - - - - - -

Manual

Means

ONLY

Door

Releases

Upon
Loss

of

Power

Visible Sign

(Within 12" of

Releasing Device)

- - - - - - - - -

Reading:

"PUSH UNTIL

ALARM SOUNDS"

"DOOR CAN BE

OPENED IN 15

SECONDS"

Table D-1