1.000A 22 20 20 18 16 14 14 12 10

.800A 22 22 20 18 18 16 14 14 12
.600A 24 22 22 20 18 18 16 14 14
.400A 24 22 22 22 20 18 18 16 14
.300A 24 24 22 22 22 20 20 18 16
.200A 24 24 24 22 22 22 20 20 18

50’

[15m]

100’

[30m]

150’

[46m]

200’

[61m]

300’

[91m]

400’

[122m]

500’

[152m]

750’

[229m]

1000’

[305m]

24VDC

WIRE DISTANCE

Table B-2

The Wire Distance indicated on the table above represents a 2-wire “One-Way”
length from the power supply source to entryway installation area.

The Gauge values specified on the table above represent a 2-wire “Round Trip”

length from the power supply source to entryway installation and returning back
to the power supply source.

IMPORTANT

THE 200’ [61m] WIRE RUN IN EACH TABLE FACTORS A 400’ [122m] ROUND TRIP