Warning, Generator lifting – Gillette Generators SP-1500 User Manual

Page 12

Advertising
background image

PAGE 12

1) Always install your generator within 20 feet from natural
gas meter or LPV vapor withdrawal tank. Further distances
may cause “starving” of fuel from generator engine, see
fuel line diameter charts on page 20.
2) Exhaust end must always be turned away or parallel
with building and minimum 5 feet away.
3) Exhaust end is not to be directed towards play areas,
patios, under canopies or overhangs, or where people or
animals congregate.
4) Do not install generator under deck of house.
5) Furnace and other habited building air intakes should
be minimum 15 feet from gen-set exhaust

end.

6) Windows and doors on adjacent walls, to be closed at all
times, during generator operation.
7) Nearest roof overhang vent or window locations should
be minimum 15 feet from exhaust end.
8) If electrical distribution center panel is far away from
gas meter or LPV tank, locate generator close to gas meter
or LPV tank. Installation costs are lower, if electric wiring
is oversized for long distances, to utility point rather than
oversized fuel lines to gas meter.

SUGGESTIONS FOR GENERATOR LOCATIONS

RECEIVING AND INSTALLATION TIPS

When you receive your weather/sound housed generator, there are several items that require immediate
attention.

A) If gen-set is shipped open with protective wrap, remove wrap and carefully inspect gen-set for any shipping

damage or missing optional equipment, before shipper leaves your premise. Note damage or missing parts on
shipper’s Bill of Lading.

B) If gen-set is shipped in wooden crate, and crate appears damaged, note this crate damage on shippers Bill of
Lading, indicating product damage may be possible due to crate damage.

C) If gen-set is to stored for a long period before use, the storage area should conform to published storage
temperature and humidity specifications.

When lift or hoist equipment is used, to lift the gen-set, be careful not to contact overhead power lines or any

other obstacles.

Hoist equipment should have appropriate tires for rough terrain to avoid becoming stuck or overturning. If
shipping pallet or wood structure is intact, use a forklift to move gen-set. If shipping material is removed, use (2)
steel pipes thru the lift point, to lift gen-set. This mounting location of gen-set is important. It must be installed in
an area that is protected from harmful gases, liquids, dust, metallic particles, shock, or vibrations. It should be

installed in an outdoor location, so that exhaust fumes are vented to the atmosphere. The factory installed
weather and sound protected enclosure is designed to keep out undesirable weather elements.

5'

5'

APPROX.

10'

OCCUPIED

BUILDING

PREFERRED

ACCEPTABLE

#1

GE

N

E

RA

TOR

#2

GENER

A

TOR

GAS

METER

DANGER

TOXIC FUMES

MAY ENTER

BUILDING

BUILDING AIR

INTAKE AREA

NO AIR

INTAKE ARE

A

FIGURE 3

WARNING

Unbalanced Weight

Improper lifting can cause

severe injury or death and

equipment damage

Do not use lifting eyes.

Lift the generator set using

lifting bars inserted through

the lifting holes on the skid.

Generator Lifting

Height

Width

Length

To lift the generator, always use spreader bars,
chains, eyehooks and other hardware that is of
sufficient strength to lift at least three times the
weight of the generators

Lifting Bars

Lifting Bars

FIGURE 2