Gillette Generators SP-1500 User Manual

Page 13

Advertising
background image

PAGE 13

WARNING: An open bottom, stationary gen-set must be installed over a non-combustible material, such as a

cement slab, and must be positioned to prevent combustible materials, rain, pooling water, sprinklers, etc. from

entering into, and accumulating under gen-set.

A) Installation should place gen-set as close as possible to the fuel supply, the transfer switch, and distribution/
circuit breaker panel.


B) Service access must be provided to allow generator housing doors to fully open.

C) Installation must prevent water, leaves, grass, snow, etc., from reaching top of generator skid base. Drainage
must be provided to keep concrete pad, free from standing water.

D) Always remove snow accumulation on roof when snow depth reaches 4”, or more.


E) Maximum ambient operating temperature is 105º F (40º C), for all gen-set sizes.

NOTE #1

NOTE #2

NOTE #3

NOTE #4

HEIGHT

NET WEIGHT

HEIGHT

NET WEIGHT

GEN-SET

MODEL

A B

C-1 C-2 D E F G H I I-1

IN.

CM.

LBS. KG IN. CM.

LBS. KG

SP-200 14 6 34 -

49

1/2 62 68 7 33 36 34 86 971 440 47 119 1371 622

SP-250 14 6 34 -

49

1/2 62 68 7 33 36 34 86 1070 485 47 119 1470 667

SP-300 14 6 34 -

49

1/2 62 68 7 36 36 34 86 1120 508 47 119 1520 689

SP-410

16 6

-

4 1/4

51 1/2 72

78

8 39 42 36

91 1326 601

53

134 1806 819

SP-520

16 6

-

4 1/4

51 1/2 72

78

8 39 42 38

97 1670 757

53

134 2150 973

SP-620

16 6

-

4 1/4

51 1/2 72

78

8 39 42 38

97 2097 951

53

134 2411 1094

SP-8005N 24 6

-

4 1/4 55 74 1/2 104

98 12 45 48 50 127 2097 943 72 1/2 183 2829 1283

SP-960

24 6

-

4 1/4 55 74 1/2 104

98 12 45 48 50 127 2229 1011 72 1/2 183 2979 1351

SP-1200 24 8

-

4 1/4 48 82 1/2 124 110 12 45 48 52 132 2424 1099 72 1/2 183 3174 1440

SP-1500 24 8

-

4 1/4 48 82 1/2 124 110 12 45 48 52 132 2684 1217 72 1/2 183 3594 1630

NOTE #1: HEIGHT FOR “OPEN” (NO ENCLOSURE) GEN-SET.

NOTE #2: NET WEIGHT FOR “OPEN” (NO ENCLOSURE) GEN-SET.

NOTE #3: HEIGHT FOR ENCLOSED GEN-SET.

NOTE #4: NET WEIGHT FOR ENCLOSED GEN-SET.

NOTE #5: ADD 18” TO HEIGHT FOR MUFFLER EXHAUST PIPE EXTENSION AND

ATTACHED RAIN CAP, ON WEATHER HOUSED SETS.
NOTE #6: WEIGHTS AND DIMENSIONS ARE APPROXIMATE AND MAXIMUM.

CONSULT FACTORY FOR EXACT FIGURES.

NOT

U

S

E

D

B

A

D

E

F

G

H

I

C-C

I-1

C-2

C-1

Battery Tray

Electrical Stub Up

(Exhaust Chute on

Enclosed Gen-Set)

(Air Intake Chute

on Enclosed

Super-Silent Gen

-Set)

External

Fuel Input

External

Fuel Input

FIGURE 4

Incoming Co

oling

Air

Advertising