TERMINAL CONNECTOR TORQUE

Use the torque values shown for terminal connectors.

Refer to UL-486A, UL-486B, and UL-486E for
information on terminal connectors for aluminum
and/or copper conductors. Comply with applicable

national and local codes when installing a wiring
system.

NOTE: If a connector has a clamp screw such as a

slotted, hexagonal head screw with more than one
means of tightening, test the connector using both
applicable torque values.

SOCKET SIZE ACROSS FLATS,

mm (in.)

TIGHTENING TORQUE,

Nm (in. lb.)

3.2 (1/8) 5.1 (45)

4.0 (5/32) 11.4 (100)

4.8 (3/16) 13.8 (120)

5.6 (7/32) 17.0 (150)

6.4 (1/4) 22.6 (200)

7.9 (5/16) 31.1 (275)

9.5 (3/8) 42.4 (375)

12.7 (1/2) 56.5 (500)

14.3 (9/16) 67.8 (600)

NOTE: For values of slot width or length not corresponding
to those specified, select the largest torque value
associated with the conductor size. Slot width is the
normal design value. Slot length is to be measured at the
bottom of the slot.

TIGHTENING TORQUE FOR PRESSURE

WIRE CONNECTORS WITH INTERNAL-

DRIVE SOCKET-HEAD SCREWS

TIGHTENING TORQUE, Nm (in. lb)

WIRE SIZE FOR UNIT

CONNECTION

SLOT HEAD 4.7 mm (NO. 10) OR LARGER *

HEXAGONAL HEAD-EXTERNAL DRIVE

SOCKET WRENCH

AWG, kcmil (mm

2

)

SLOT WIDTH >1.2 mm (0.047 in.)

SLOT LENGTH > 6.4 mm (0.25 in.)

SLOT WIDTH >1.2 mm (0.047 in.)

SLOT LENGTH > 6.4 mm (0.25 in.)

SPLIT-BOLT

CONNECTORS

OTHER

CONNECTIONS

18-10 (0.82-5.3)

2.3

(20)

4.0

(35) 9.0

(80)

8.5

(75)

8 (8.4) 2.8 (25) 4.5 (40)

9.0

(80)

8.5

(75)

6-4 (13.3-21.2) 4.0

(35)

5.1

(45) 18.6

(165)

12.4

(110)

3 (26.7) 4.0 (35) 5.6 (50)

31.1

(275)

16.9

(150)

2 (33.6) 4.5 (40) 5.6 (50)

31.1

(275)

16.9

(150)

1 (42.4)

-

5.6 (50)

31.1

(275)

16.9

(150)

1/0-2/0 (53.5-67.4)

-

5.6

(50)

43.5 (385) 20.3 (180)

3/0-4/0 (85.0-107.2)

-

5.6

(50) 56.5

(500)

28.2

(250)

250-350 (127-177)

-

5.6

(50) 73.4

(650)

36.7

(325)

400 (203)

-

5.6 (50)

93.2

(825)

36.7

(325)

500 (253)

-

5.6 (50)

93.2

(825)

42.4

(375)

600-750 (304-380)

-

5.6

(50) 113.0

(1000)

42.4

(375)

800-1000 (406-508)

-

5.6

(50) 124.3

(1100)

56.5 (500)

1250-2000 (635-1016)

-

-

124.3 (1100) 67.8 (600)

* For values of slot width or length not corresponding to those specified, select the largest torque value associated with the
conductor size. Slot width is the normal design value. Slot length is to be measured at the bottom of the slot.

NOTE: If a connector has a clamp screw such as a slotted, hexagonal head screw with more than one means of tightening, test
the connector using both applicable torque values.

TIGHTENING TORQUE FOR SCREW-TYPE PRESSURE WIRE CONNECTORS

Advertising
This manual is related to the following products: