CHQ-DSC DUAL SOUNDER CONTROLLER provides two independent sounder outputs with open and short circuit monitoring (which
can be disabled). The sounder outputs can be separately driven, continuously or pulsed, under full synchronisation of the fire alarm
panel with other sounders on the same loop. An input is provided with short and open circuit monitoring (which can be disabled).

Setting Sounder & Input Monitoring

8-Way DIL Switch

CHQ MODULE

SWITCH 8 UP

I/P Monitoring Disabled

SWITCH 8 DOWN I/P Monitoring Enabled

DIN MODULE

SWITCH 8 UP

I/P Monitoring Enabled

SWITCH 8 DOWN I/P Monitoring Disabled

2-Way DIL Switch

CHQ MODULE

SWITCH 1 UP

SNDR O/P 1 Monitoring Disabled

SWITCH 1 DOWN SNDR O/P 1 Monitoring Enabled
SWITCH 2 UP

SNDR O/P 2 Monitoring Disabled

SWITCH 2 DOWN SNDR O/P 2 Monitoring Enabled

DIN MODULE

SWITCH 1 UP

SNDR O/P 1 Monitoring Enabled

SWITCH 1 DOWN SNDR O/P 1 Monitoring Disabled
SWITCH 2 UP

SNDR O/P 2 Monitoring Enabled

SWITCH 2 DOWN SNDR O/P 2 Monitoring Disabled

This module requires an auxiliary 24 Vdc power supply (this can also be
monitored) - see Fig 4.

Order codes

CHQ-DSC(SCI) / CHQ-DSC/M(SCI) / CHQ-DSC/DIN(SCI)*

1

Transmission method

Digital communications using ESP

Loop:

Operating voltage

17 - 41 Vdc

Quiescent current

290

A

Current consumption whilst polling

22 mA

20 %

Current in short-circuit

8 mA

Maximum short-circuit current (Loop)

1 A

External Supply:-Operating voltage

20-28.8 Vdc (24 Vdc nominal)

Current consumption (per line)

Sounder On - 8 mA, Sounder Fault - 6 mA

Sounder output current

1 A/line max

Sounder line capacitance

0.3

F/line max.

Sounder E.O.L resistor

1 k

,

5%, 2 W

Input E.O.L resistor

10 k

,

5%, 0.25 W

Input threshold levels

ON=470

, short cct< 50

, open cct>100 k

,

Weights (g) &
Dimensions (mm)

CHQ-DSC(SCI)

360

L=157 x W=127 x D=35 (CHQ Module plus Lid)
D=79 (CHQ Module plus Lid plus CHQ-BACKBOX)
(add 235 to module weight when using CHQ-BACKBOX)

CHQ-DSC/DIN(SCI)

145

L=119 x W=108 x D=24

Colour and enclosure material

CHQ Module & CHQ-BACKBOX White ABS, DIN Module Green ABS

*

1

Fire alarm control panel compatibility required for these products. See AP0127 for short circuit isolator specifications.

Note:- All EOL and operational resistors are supplied with the unit

– DO NOT DISCARD IN ERROR!





Protocol specified in
TI/006

CHQ-DSC/(SCI)

CHQ-DSC(HFP)-SCI

0832-CPD-1102

*1

09

EN54-17 Short Circuit Isolators
EN54-18 Input/Output Modules

CHQ-DSC/DIN(SCI)

0832-CPD-1103

*1

10

EN54-17 Short Circuit Isolators
EN54-18 Input/Output Modules

CHQ-MRC2(SCI)

CHQ-MRC2(HFP)-SCI

0832-CPR-F0058/13

*1

13

EN54-17 Short Circuit Isolators
EN54-18 Input/Output Modules

CHQ-MRC2/DIN(SCI)

0832-CPR-F0059/13

*1

13

EN54-17 Short Circuit Isolators
EN54-18 Input/Output Modules

*1

For Declarations of Performance visit www.hochikieurope.com



Fig 4

LOOP CONNECTIONS

S = Cable Screen (if required)
- = Loop Negative (-ve)
+ = Loop Positive (+ve)

Advertising