Chq-mrc2 – Hochiki CHQ-DSC/M(SCI) User Manual

Page 3

Advertising
background image

Hochiki Europe (UK) Ltd

Page 3

2-3-0-1730/ISS3/DEC13

CHQ-DRC2 DUAL RELAY CONTROLLER

is a loop powered input/output module with two independent N/O and N/C volt free

change over relay outputs which can be driven separately. Used for the control of devices such as dampers or for plant and
equipment shutdown. A single input is also provided for local fire and fault monitoring which is fully monitored for open and short
circuit (can be disabled).

Setting Fault Monitoring

8-Way DIL Switch

CHQ MODULE

SWITCH 8 UP

Monitoring Disabled

SWITCH 8 DOWN Monitoring Enabled

DIN MODULE

SWITCH 8 UP

Monitoring Enabled

SWITCH 8 DOWN Monitoring Disabled

Note:- The state of the relay contacts will be indeterminate until the
unit is powered.

Order codes

CHQ-DRC2(SCI) / CHQ-DRC2/DIN(SCI)*

Transmission method

Digital communication using ESP

Loop:

Operating voltage

17 - 41 Vdc

Quiescent current

300

A

Current consumption whilst polling

22 mA

20 %

Current in short-circuit

8 mA

Maximum short-circuit current (Loop)

1 A

Relay contact rating

30 Vdc max, 1 A (resistive load)

Input E.O.L resistor

10 k

,

5%, 0.25 W

Input threshold level

ON=470

, Short cct <50

, Open cct >100 k

Weights (g) and
Dimensions (mm):

CHQ-DRC2(SCI)

346

L=157 x W=127 x D=35 (CHQ Module plus Lid)
D=79 (CHQ Module plus Lid plus CHQ-BACKBOX)
(add 235 to module weight when using CHQ-BACKBOX)

CHQ-DRC2/DIN(SCI)

124

L=119 x W=108 x D=24

Colour and enclosure material

CHQ Module & CHQ-BACKBOX White ABS, DIN Module Green ABS

*1 Fire alarm control panel compatibility required for these products. See AP0127 for short circuit isolator specifications.
Note:- All EOL and operational resistors are supplied with the unit

– DO NOT DISCARD IN ERROR!

CHQ-MRC2 MAINS RELAY CONTROLLER is a loop powered input/output module, with a single mains-rated change-over relay
output, which has the N/O, N/C and COMMON contacts available via screw terminal contacts. This output is driven under the control
of the fire alarm panel and can be used for the control of devices such as dampers or for plant and equipment shutdown. A single
input is also provided for local fire and fault monitoring and this is fully monitored for open and short circuit (can be disabled). Note:-
The state of the relay contacts will be indeterminate until the unit is powered.

Setting Input Monitoring

8-Way DIL Switch

CHQ MODULE

SWITCH 8 UP

Monitoring Disabled

SWITCH 8 DOWN Monitoring Enabled

DIN MODULE

SWITCH 8 UP

Monitoring Enabled

SWITCH 8 DOWN Monitoring Disabled

Order codes

CHQ-MRC2(SCI) / CHQ-MRC2/DIN(SCI)*

Transmission method

Digital communication using ESP

Loop:

Operating voltage

17 - 41 Vdc

Quiescent current

300

A

Current consumption whilst polling

22 mA

20 %

Relay contact rating**

48 Vdc max, 2 A (resistive load), 250 Vac max, 5 A (resistive load)

– For mains AC switching,

the Control Panel must be compliant with Low Voltage Directive for SELV circuits.

Input E.O.L resistor

10 k

,

5%, 0.25 W

Input threshold level

ON=470

, Short cct <50

, Open cct >100 k

Weights (g)
and
Dimensions
(mm)

CHQ-MRC2(SCI)

133

L=190 x W=90 x D=25

CHQ-MRC2/DIN(SCI)

121

L=119 x W=108 x D=24

Colour and enclosure material

Adaptor Plate and PCB cover white ABS and Polycarbonate, DIN Module Green ABS

To ensure compliance with EN54-17:2005 and EN54-18:2005 is maintained the CHQ-MRC2(SCI) & CHQ-MRC2/DIN(SCI) must be installed within an enclosure weighing greater than 4.75kg. The
enclosure should have an ingress protection rating of IP65 or greater.
*1 Fire alarm control panel compatibility required for these products. See AP0127 for short circuit isolator specifications.
Note:- All EOL and operational resistors are supplied with the unit

– DO NOT DISCARD IN ERROR!

Fig 6

Fig 5

CHQ-MRC2

(all variants)

** No fuses are fitted on this device. The relay output circuit must
therefore be protected by a suitable over-current protection device to
prevent excessive current through the relay contacts. Refer to the relay
contact specification in this document.