J. DIAGRAMS FOR VERTICAL VENTING

Figure 26

– Venting

PART 8 – GAS PIPING

Failure to follow all precautions in this section could result in fire, explosion, severe injury or death!

A. GAS CONNECTION

Connect the gas supply to the system following state and local plumbing codes. Use the supplied ball valve at the inlet to the system.
Make sure the gas supply line fits as shown in Figure 27.

The gas supply shall have a maximum inlet pressure of less than 14" water column (350 mm), ½ pound pressure (3.5 kPa), and a
minimum of 3.5" water column. The entire piping system, gas meter and regulator must be sized properly to prevent pressure drop
greater than 0.5" WC as stated in the National Fuel Gas Code. This information is listed on the rating plate.

NOTE:

Maximum inlet gas pressure must not exceed 14” w.c. (3.5 kPa).