INSPECTION ACTIVITIES

DATE LAST COMPLETED

PIPING

1

st

YEAR

2

nd

YEAR

3

rd

YEAR

4

th

YEAR*

Near heater piping

Check heater and system piping for any sign of leakage, make
sure they are properly supported.

Vent

Check condition of all vent pipes and joints.

Gas

Check Gas piping, test for leaks and signs of aging. Make sure
all pipes are properly supported.

SYSTEM
Visual

Do a full visual inspection of all system components.

Functional

Test all functions of the system (Heat, Safeties)

Temperatures

Verify safe settings on heater or Anti-Scald Valve

Temperatures

Verify programmed temperature settings

ELECTRICAL
Connections

Check wire connections. Make sure they are tight.

Smoke and CO
detector

Verify devices are installed and working properly. Change
batteries if necessary.

Circuit Breakers

Check to see that the circuit breaker is clearly labeled. Exercise
circuit breaker.

CHAMBER/BURNER
Combustion Chamber

Check burner tube and combustion chamber coils. Clean
according to maintenance section of manual. Vacuum
combustion chamber.

Spark Electrode

Clean. Set gap at ¼”.

Flame Probe

Clean. Check ionization in uA (d7 on status menu in Start-up
Procedures). Record high fire and low fire.

CONDENSATE
Neutralizer

Check condensate neutralizer. Replace if necessary.

Condensate hose

Disconnect condensate hose. Clean out dirt. Fill with water to
level of outlet and re-install. (NOTE: Verify the flow of
condensate, making sure that the hose is properly connected
during final inspection.)

GAS
Pressure

Measure incoming gas pressure (

3.5” to 14” W.C.)

Pressure Drop

Measure drop in pressure on light off (no more than 1” W.C.)

Check gas pipe for
leaks

Check piping for leaks. Verify that all are properly supported.

COMBUSTION
CO/CO2 Levels

Check CO and CO2 levels in Exhaust (See Start-up Procedures
for ranges). Record at high and low fire.

SAFETIES
ECO (Energy Cut Off)

Check continuity on Flue and Water ECO. Replace if corroded.

Water Pressure Switch

Check operation and for signs of leakage. Replace if corroded.

Thermistors

Check wiring. Verify through ohms reading.

FINAL INSPECTION
Check list

Verify that you have completed entire check list. WARNING:
FAILURE TO DO SO COULD RESULT IN SERIOUS INJURY
OR DEATH.

Homeowner

Review what you have done with the homeowner.

Table 19 -

*Continue annual maintenance beyond the 4

th

year as required.