Home Return and Movement after Start (PIO Pattern = “1: [Standard]”)


First, force the position complete signal to turn ON by referring to 7.1, “How to Start.”
If home return has not yet been executed immediately after the system start, issuing a start command by
specifying a position will cause the actuator to return to the home before moving to the specified position.
Example of use in operation) Home return is performed after the power ON, followed by positioning to the

position 150 mm from the home at a speed of 200 mm/sec.

Position-data table (Field(s) within thick line must be entered.)

No. Position

Speed

Acceleration/

deceleration

Push Positioning

band

Acceleration

only MAX

0

0 100

0.3 0 0.1 0

1

150

200

0.3 0 0.1 0

RCP2 controller






































P


L


C

[5] [2]

[1]












[8]




[7] [3]

[6]




[9] [4]

PIO

Signal name

Start

Command position 1

Command position 2

Command position 4

Command position 8

*Pause

Reset

Servo ON

Completed position 1

Completed position 2

Completed position 4

Completed position 8

Position complete

Home return completion

Zone

*Alarm

Ready

Moving

Category

Input















Output

Reference flow

Power ON

Select/enter command position 1.

[1]


[2]


[3]


[4]


[5]


[6]



[7]


[8]


[9]

Start input ON

Home return starts

Position complete output OFF

Moving output ON

Start input OFF

Home return completes.

Home return completion output ON

Movement to position 1 starts.

Position complete output turns ON 0.1 mm
before position 1.

Completed position 1 is output.

Moving output OFF

Movement to position 1 completes.