2 example for parameter settings – IAI America XSEL-S User Manual
Page 24

3. XSEL-R/S/RX/SX/RXD/SXD
18
3.5.2 Example for Parameter Settings
(1) Example for when using EtherNet/IP
It is how to establish the setting when using EtherNet/IP to 16 ports of each input and output
from the top of the standard I/O ports, and no other I/O port (for I/O board, etc.) is to be used.
Ɣ I/O Parameter
No.
Parameter name
Default
(reference)
Input Range
Unit
Remarks
1 I/O Port Allocation Type
1
0 to 1
0
0: Fixed Allocation
1: Automatic Allocation
• Reference 1 Priority of I/O Port Assignment
when automatically assigned
Port No.
(No.0 to 299/No.300 to 599)
1) Network I/F Module 1
2) I/O slot 1 (I/O1) Mounting board
3) I/O slot 2 (I/O2) Mounting board
* Assigned for the range of continuous
mounting from I/O slot 1 (I/O1) Mounting
board
• Reference 2 Priority of extension I/O ports
at automatic assignment
Port No.
(No.1000 to 3999/
No.4000 to 6999)
1) Network I/F Module 2
2) Extension I/O Unit
3) IA Net
2 Standard I/O Fix-Allocated
Input Port Start No.
0
-1 to 599
-1
0+(Multiples of 8)
[Ineffective when -1 is selected]
3 Standard I/O Fix-Allocated
Output Port Start No.
300
-1 to 599
-1
300+(Multiples of 8)
[Ineffective when -1 is selected]
10 Standard I/O Error Monitoring
(I/O1)
1
0 to 5
0
0: No Monitoring (Not to use I/O board)
1: Monitoring
2: Monitoring (Not to monitor 24V I/O power
related error)
3: Monitoring (To monitor only 24V I/O power
related error)
14 Network I/F Module 1
Remote Input Ports
0
0 to 256
16 8 port unit
15 Network I/F Module 1
Remote Output Ports
0
0 to 256
16 8 port unit
16
Network I/F Module 1
Fix-Allocated Input Port Start
No.
-1
-1 to 599
0 0+(Multiples of 8)
[Ineffective when -1 is selected]
Not to be used
(I/O Board)
Standard Input Port No.0 to 15
Standard Output Port No.300 to 315
(EtherNet/IP Board)