2 example for parameter settings – IAI America XSEL-S User Manual

Page 24

Advertising
background image

3. XSEL-R/S/RX/SX/RXD/SXD

18

3.5.2 Example for Parameter Settings

(1) Example for when using EtherNet/IP

It is how to establish the setting when using EtherNet/IP to 16 ports of each input and output

from the top of the standard I/O ports, and no other I/O port (for I/O board, etc.) is to be used.



Ɣ I/O Parameter



No.

Parameter name

Default

(reference)

Input Range

Unit

Remarks

1 I/O Port Allocation Type

1

0 to 1

0

0: Fixed Allocation

1: Automatic Allocation

• Reference 1 Priority of I/O Port Assignment

when automatically assigned

Port No.

(No.0 to 299/No.300 to 599)

1) Network I/F Module 1

2) I/O slot 1 (I/O1) Mounting board

3) I/O slot 2 (I/O2) Mounting board

* Assigned for the range of continuous

mounting from I/O slot 1 (I/O1) Mounting

board

• Reference 2 Priority of extension I/O ports

at automatic assignment

Port No.

(No.1000 to 3999/

No.4000 to 6999)

1) Network I/F Module 2

2) Extension I/O Unit

3) IA Net

2 Standard I/O Fix-Allocated

Input Port Start No.

0

-1 to 599

-1

0+(Multiples of 8)

[Ineffective when -1 is selected]

3 Standard I/O Fix-Allocated

Output Port Start No.

300

-1 to 599

-1

300+(Multiples of 8)

[Ineffective when -1 is selected]

10 Standard I/O Error Monitoring

(I/O1)

1

0 to 5

0

0: No Monitoring (Not to use I/O board)

1: Monitoring

2: Monitoring (Not to monitor 24V I/O power

related error)

3: Monitoring (To monitor only 24V I/O power

related error)

14 Network I/F Module 1

Remote Input Ports

0

0 to 256

16 8 port unit

15 Network I/F Module 1

Remote Output Ports

0

0 to 256

16 8 port unit

16

Network I/F Module 1

Fix-Allocated Input Port Start

No.

-1

-1 to 599

0 0+(Multiples of 8)

[Ineffective when -1 is selected]

Not to be used

(I/O Board)

Standard Input Port No.0 to 15

Standard Output Port No.300 to 315

(EtherNet/IP Board)