Part 1 Specification

Chapter 3 Gateway R unit

130

Part 1 Specification

[2] Read response command data 0 to 3

z

Query

Field name

RTU mode data

(8 bits)

Data length

(bytes)

Remarks

Header

None

-

Slave address

3F H

1

Fixed.

Function code

03 H

1

Starting address

(upper)

F7 H

Starting address

(lower)

02 H

2

Initial address of the response command

Number of registers (upper)

00 H

Number of registers (lower)

05 H

2

Number of registers (1 register = 1 word): 5

Error check

(CRC)

Based on

calculation result

2

(12 A3)

Trailer

None

-

Total bytes

8

z

Response

Field name

RTU mode data

(8 bits)

Data length

(bytes)

Remarks

Header

None

-

Slave address

3F H

1

Fixed.

Function code

03 H

1

Data bytes

0A H

1

1-word register x 5 = 10 bytes

Data 1 (upper)

(lower)

Response

command

2

Data 2 (upper)

(lower)

Data 0

2

Data 3 (upper)

(lower)

Data 1

2

Data 4 (upper)

(lower)

Data 2

2

Position number specified in the request

command

Data 5 (upper)

(lower)

Data 3

2

Address

Error check

(CRC)

Based on

calculation result

2

Trailer

None

-

Total bytes

z

Actual Example (Example of reading the response data after issuing a command to read the table position for position

No. 2 of axis 0)

„

Sent Query:

3F03F702000512A3

„

Received Response: 3F030A

1040

0002

2710

0000

0000

A74A

[1]

[2]

[3]

[4]

[5]

(Explanation) [1] The response command is “1040H,” meaning that this is a target position read command.

[2] Position number: 2

[3] Lower word of position data that has been read: 2710H

[4] Upper word of position data that has been read: 0000H

[5] Axis number: 0

2710H = 10000 (decimal)

o

100.00 mm

-154-