NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) 

Remote Emergency Power Off (REPO) Port 

A customer supplied switch located remotely can be used to open the REPO connection and allows the 
UPS output receptacles to be switched off. Since the REPO shuts down the equipment immediately, 
orderly shutdown procedures are not followed by any power management software. The UPS will have 
to be manually restarted in order to regain power to the outlets on the UPS. 

DETERMINING THE POWER REQUIREMENTS OF YOUR 
EQUIPMENT
 

1. Make sure the total Volt‐Amp (VA) requirements of your connected equipment does not exceed 

the maximum VA rating for the UPS. The maximum VA ratings are shown in the Specifications 
section of this document. 

2. Ensure that the equipment plugged into the battery‐powered outlets does not exceed the UPS 

rated capacity. If UPS rated capacities are exceeded, an overload condition may occur and cause 
the UPS to shut down and trip the circuit breaker. 

3. If  the  power  requirements  of  your  equipment  are  listed  in  values  other  than  Volt‐Amps  (VA), 

convert  Watts  (W)  or  Amps  (A)  into  VA  by  doing  the  calculations  below.  Note:  The  equation 
below  only  calculates  the  maximum  amount  of  VA  that  the  equipment  can  use,  not  what  is 
typically used by the equipment at any given time. Users should expect usage requirements to 
be approximately 60% of the value to estimate power requirements: 

Watts (W) x 1.43 = _____ VA or _____ Amps (A) x 120 = _____ VA 

Add the totals for all of the equipment and multiply this total by 0.65 to calculate actual power 
requirements. 

Note: Many factors can affect the amount of power that your computer system will require. The 
total load that you will be placing on the battery‐powered outlets should not exceed 85% of the 
UPS capacity. 