23

FIGURE 16

ACCEL/DECEL "2" CONENCTIONS

TABLE 10

ACCEL/DECEL "2" PROGRAMMING

Function No.

Code/Range

7.05: Multi-Function Input Terminal 6 0005:

Accel/Decel 2

7.16: Accel/Decel 2 Time 0.3

180.0:

Set to Desired Time*

*Factory set to 1.5 seconds.

4.4 FORWARD/STOP-REVERSE/STOP

Remote Forward/Stop and Reverse/Stop operation can be performed by
connecting switches or contacts to the Multi-Function Input Terminals. See
Figure 17, on page 24, for connections. See Table 11, on page 24, for drive
programming.


Connect the Start/Stop Switch or Contact to Multi-Function Input Terminal "5",
which is factory set for N.O. Start ("0010"). Connect the Forward/Stop and
Reverse/Stop Switches or Contacts to any Multi-Function Input Terminals
"1" – "7". Terminals "3" and "4" have been arbitrarily chosen for Forward/Stop
and Reverse Stop. Connect the common of the switches or contacts to any
available common terminal ("8", "12", "14", "16", "18", "20", "22").


Operation: When the Forward/Stop Switch or Contact is closed, the drive will run
in the forward direction. When the Forward/Stop Switch or Contact is opened,
the drive will stop. When the Reverse/Stop Switch or Contact is closed, the drive
will run in the reverse direction. When the Reverse/Stop Switch or Contact is
opened, the drive will stop.