LEESON Sub-Micro Dynamic Braking Kit for Ext Resistor User Manual

Sub-micro series dynamic braking option, Sm-plus series drives, Sm series drives

Advertising
background image

SUB-MICRO SERIES DYNAMIC BRAKING OPTION

(FOR USE WITH EXTERNAL RESISTORS)

INSTALLATION AND OPERATION INSTRUCTIONS

Manual Number: SDBN06C

(These instructions apply to Dynamic Braking modules 174417, 174418, and 174419 ONLY)

The Sub-Micro Series Dynamic Braking option can be used with all SM, SM-Plus, and SM-Basic models.

SM-PLUS SERIES DRIVES

PROGRAMMING

1.

Set Parameter 09 (TB-31 OUTPUT) to DYNAMIC BRAKING (04).

WIRING

The diagram to the right illustrates how the DB module is wired to the SM-Plus Series
drive.

NOTE 1: Use 18 AWG wire for control connections.
NOTE 2: Use minimum 14 AWG wire for connections to B+, B-, R+, and R-. The B+

and B- wires MUST be twisted together and must be less than 12 inches
long. Twisting the R+ and R- wires is also recommended.

NOTE 3: External resistors are required when using Dynamic Braking modules 174417,

174418, and 174419. External resistor assemblies are available from LEESON
(refer to the resistor selection chart on the next page).

SM-PLUS

POWER

TERMINALS

SM-PLUS

CONTROL

TERMINALS

42

46

47

43

DB OPTION MODULE

31

2

GND

B -

B + R +

R -

B -

B +

SM-PLUS DIAGRAM

EXTERNAL
RESISTORS

(SEE NOTE 3)

WARNING!

Remove power from the drive and wait three minutes before wiring the DB module. Incorrect wiring of the B+ and B- terminals will result in
equipment damage!
The B+ terminal on the DB module must be connected to the B+ terminal on the Sub-Micro drive, and the B- terminal on the DB
module must be connected to the B- terminal on the Sub-Micro drive.

!

SM SERIES DRIVES

PROGRAMMING

1.

Set Parameter 12 (TB-13E FUNCTION) to DYNAMIC BRAKING (20).

WIRING

The diagram to the right illustrates how the DB module is wired to the SM Series drive.

NOTE 1: Use 18 AWG wire for control connections.
NOTE 2: Use minimum 14 AWG wire for connections to B+, B-, R+, and R-. The B+

and B- wires MUST be twisted together and must be less than 12 inches
long. Twisting the R+ and R- wires is also recommended.

NOTE 3: External resistors are required when using Dynamic Braking modules 174417,

174418, and 174419. External resistor assemblies are available from LEESON
(refer to the resistor selection chart on the next page).

SM

POWER

TERMINALS

SM

CONTROL

TERMINALS

42

46

47

43

DB OPTION MODULE

13E

GND

B -

B + R +

R -

B -

B +

SM DIAGRAM

2

EXTERNAL
RESISTORS

(SEE NOTE 3)

LEESON Electric

LEESON Electric

LEESON Electric

LEESON Electric

LEESON Electric • 2100 Washington St. • Grafton, WI 53024 • Ph: (262) 377-8810 • Fax: (262) 377-9025 • www.leeson.com

Advertising