SUB-MICRO SERIES DYNAMIC BRAKING OPTION

(FOR MODELS RATED 0.25 - 10 HP)

INSTALLATION AND OPERATION INSTRUCTIONS

Manual Number: SDBR06C

The Sub-Micro Series Dynamic Braking option can be used with all SM, SM-Plus and SM-Basic models.

WARNING!

Remove power from the drive and wait three minutes before wiring the DB module. Incorrect wiring of the B+ and B- terminals will result in
equipment damage!
The B+ terminal on the DB module must be connected to the B+ terminal on the Sub Micro drive, and the B- terminal on the DB
module must be connected to the B- terminal on the Sub-Micro drive.

DO NOT make connections to R+ and R- without consulting LEESON. Damage to the Dynamic Braking module and/or drive may result.

!

SM-PLUS SERIES DRIVES

PROGRAMMING

1.

Set Parameter 09 (TB-31 OUTPUT) to DYNAMIC BRAKING (04).

2.

Set Parameter 10 (TB-13A FUNCTION) to DB FAULT (09), or set Parameter 12
(TB-13C FUNCTION) to DB FAULT (08).

WIRING

The diagram to the right illustrates how the DB module is wired to the SM-PLUS Series
drive. In this diagram, TB-13A is used as the DB FAULT input, but TB-13C could be
used instead if TB-13A is required for another function.

NOTE 1: Use 18 AWG wire for control connections.
NOTE 2: Use minimum 14 AWG wire for connections to B+ and B-. The B+ and B-

wires MUST be twisted together and must be less than 12 inches long.

NOTE 3: DO NOT make connections to R+ and R- without consulting LEESON.

Damage to the Dynamic Braking module and/or drive may result.

SM-PLUS

POWER

TERMINALS

SM-PLUS

CONTROL

TERMINALS

42

46

47

43

DB OPTION MODULE

13A

2

31

GND

B -

B + R +

R -

B -

B +

SM-PLUS DIAGRAM

(SEE NOTE 3)

SM SERIES DRIVES

PROGRAMMING

1.

Set Parameter 12 (TB-13E FUNCTION) to DYNAMIC BRAKING (20).

2.

Set Parameter 10 (TB-13A FUNCTION) to INVERSE EXT. FAULT (09), or set
Parameter 11 (TB-13B FUNCTION) to INVERSE EXT. FAULT (10).

WIRING

The diagram to the right illustrates how the DB module is wired to the SM Series drive.
In this diagram, TB-13A is programmed for INVERSE EXTERNAL FAULT, but TB-
13B could be used instead if TB-13A is required for another function.

NOTE 1: Use 18 AWG wire for control connections.
NOTE 2: Use minimum 14 AWG wire for connections to B+ and B-. The B+ and B-

wires MUST be twisted together and must be less than 12 inches long.

NOTE 3: DO NOT make connections to R+ and R- without consulting LEESON.

Damage to the Dynamic Braking module and/or drive may result.

SM

POWER

TERMINALS

SM

CONTROL

TERMINALS

42

46

47

43

DB OPTION MODULE

13A

13E 11

GND

B -

B + R +

R -

B -

B +

SM DIAGRAM

(SEE NOTE 3)

2