Vanguard ATO-600 User Manual

Page 16

Advertising
background image

ATO-400 / ATO-600 Operating Procedures

16

5.0 ATO CABLE CONNECTION

The ATO is supplied with 15-foot (#1/0 AWG) current-carrying cables and 15-foot voltage-
sensing cables. Both cables are terminated with heavy-duty alligator clamps to connect to the
device being tested. A typical cable connection for the ATO to a device under test is shown in
figure 6 and figure 7. To protect the ATO against static discharge in the substation, always
connect the unit’s ground stud to the substation ground. It is also highly recommended to ground
one side of the circuit breaker bushing during testing to eliminate any static discharge through
the ATO.

NOTE

The sense input is not polarity sensitive. The sense cables may be

connected to either input without affecting circuit operation.

Figure 6 ATO-400 Connection Diagram

Figure 7 ATO-600 Connection Diagram

Advertising
This manual is related to the following products: