ATO-400 / ATO-600 Operating Procedures

39

Table 12.0 Calibration Test Procedure (Continued)

STEP

ACTION

ATO DISPLAY

12-25

The ATO will measure the 1900

?

-ohm

shunt using 10A test current.

12-26

Observe test results. Press “ENTER” key to
continue.

12-27

The ATO will measure the 1900

?

-ohm

shunt using 100A test current.

12-28

Observe test results. Press “ENTER” key to
continue.

12-29

The ATO returns to the START MENU.

1. RUN TEST 04/11/05
2. SETUP 12:26:01
3. DIAGNOSTIC

FINAL RESISTANCE
I= 99.9 AMPS
1900.1 MICRO-OHM
ANY KEY TO CONTINUE

FINAL RESISTANCE
I= 9.9 AMPS
1900.1 MICRO-OHM
ANY KEY TO CONTINUE

CURRENT: 100.0 AMP
BURN IN: 02 SEC
1900

? -OHM TEST

CURRENT: 10.0 AMP
BURN IN: 02 SEC
1900

? -OHM TEST