Vanguard CT-6500 S2 User Manual

Page 14

Advertising
background image

CT-6500 Series 2 Operating Instructions

13

Table 1.0 CT-6500 Controls and Displays

Fig. 1.0

Index

no.

PANEL MARKING

FUNCTIONAL DESCRIPTION

1-11 &

31

CONTACT INPUT

(C1–C12)

Female connectors for the contact channels.

12

0-300V

V1

3-pin connector. V1 voltage input channel is dedicated to
monitor circuit breaker DC power supply or coil voltages.
Voltage sensing range is from 0-255 volts, dc or peak
ac.

13, 16,

19

D1, D2, D3

TRANSDUCER INPUT

16-pin connectors. Digital travel transducer input
channels.

14

0-300V

V2

3-pin connector. V2 voltage input channel is dedicated to
detect voltage on/off status (present or absent) of an A/B
switch. Voltage input ranges from 0-300 volts, dc or
peak ac.

15

0-300V

TRIGGER

3-pin connector. Triggers voltage input for external
trigger application. Voltage levels ranging from 30 to 300
V, dc or peak ac.

17

GROUND

Safety, ground terminal. 5/16-18 thread stud, with wing
nut.

18

120/240Vac, 2A, 50-60Hz

Fuse: 250V 3A, Fast Blow

3-wire power plug. 3 Ampere, AC fuses. The ON/OFF
switch is a 2-pole rocker.

20

INITIATE

4-pin connector used for the switching circuit for
operating the circuit breaker under test.

21

OPEN

250V, 5A FAST-BLOW

Open circuit fuse: 5 Ampere, 250V, Fast-Blow.

22

CLOSE

250V, 5A FAST-BLOW

Close circuit fuse: 5 Ampere, 250V, Fast-Blow.

23

“PUSH” TO ARM

Spring-loaded, pushbutton switch. Press and hold to
complete the Trip or Close circuits for breaker tests.

24

(Printer; No panel marking)

Thermal printer. Microprocessor controlled printer that
uses specially treated, 4.5 inch wide paper.

Advertising