CT-6500 Series 2 Operating Instructions

29

9.1.2 Timing an OPEN Operation with Insertion Resistors

The CT-6500 can time breakers with insertion resistors. The insertion resistor can

range from 10 to 7,000 Ohms. Any insertion resistor more than 7,000 Ohms is detected as
an open circuit. The timing results will show the main contact time and the insertion
resistor contact time. Graphic reports will show the main contact and the resistor contact
activities on each of the channels.

Table 4.0 Open Operation With Insertion Resistor

STEP OPERATION

ACTION DISPLAY

1

READY TIMER FOR BREAKER OPERATION.

PRESS #1 KEY.

INSERTION RESISTOR?

1.NO

2.YES

2

SELECT INSERTION RESISTOR.

PRESS #2 KEY.

RESISTOR VALUE:

1.LESS THAN 1000 OHM

2.1000 to 2000 OHM

3.MORE THAN 2000 OHM

3

SELECT LESS THAN 1000 OHM RESISTOR

RANGE.

PRESS #1 KEY.

TIMING WINDOWS:

1.WINDOW = 1 SEC

2.WINDOW = 10 SEC

3.WINDOW = 20 SEC

4

SELECT 1-SECOND WINDOW.

PRESS #1 KEY.

TRIGGER MODE:

1. Internal Trigger

2. External Trigger

5

SELECT INTERNAL TRIGGER.

PRESS #1 KEY.

TIMING MODE:

1. OPEN

2. CLOSE

3.

O-C

4.

C-O

5. O-C-O

6

SELECT OPEN OPERATION.

PRESS #1 KEY.

OPEN TIMING

Hold "ARM" Switch,

Then "START".

"STOP" to ABORT

7

INITIATE OPEN COMMAND.

HOLD THE "ARM"

SWITCH AND

PRESS THE "START"

KEY.

TEST IN PROGRESS

Hold "ARM" Until

Test complete.

(Up to 25 seconds)

8

ANALYZER IS READY TO OUTPUT RESULTS.

NONE.

1.RUN TEST 06/12/07

2.GET RSLT 19:20:01

3.SET-UP

4.DIAGNOSTIC

Go to section 9.2 to print a test report.