Ct-7000 operating instructions – Vanguard CT-7000 User Manual

Page 36

Advertising
background image

CT-7000 Operating Instructions

29

9.3 Get Graphic Timing Results Using the Thermal Printer

Selecting the “PLOT FULL CHART” command will plot the timing chart as follows:

Timing chart from 0 to 1000 ms with one second window and 50 ms time markers.

Timing chart from 0 to 10 seconds with 10 second window and 500 ms time markers.

Timing chart from 0 to 20 seconds with 20 second window and one second time markers.

Table 9.0 Plot Chart and Tabulated Report

STEP

OPERATION

ACTION

DISPLAY

1

GET TIMING RESULTS.

PRESS #2 KEY.

1. PRINT TEST RESULTS

2. PLOT FULL CHART

3. PLOT EXPANSION

4. PLOT 0-200 MS

2

PLOT FULL CHART.

PRESS #2 KEY.

SELECT PRINTER

1. INTERNAL THERMAL

2. EXTERNAL INK JET

3

SELECT THERMAL PRINTER.

PRESS #1 KEY.

PLEASE WAIT

PLOTTING GRAPH

4

RETURN TO MAIN MENU AFTER PRINT

CHART.

NO ACTION.

1. TIME BRKR

2. GET RSLT

3. SET UP

4. DIAGNOSTIC

NOTE

1. Plot Expansion, which is Selection #3, in Step 1, allows the user to expand the graphic
results in 100 ms increments.

2. Selecting “PLOT 0-200 MS” will automatically plot the timing chart from 0 to 200
milliseconds in the expansion mode with 10 ms timing markers, which can be seen in
Figure 14.0.

3. Graphical result interpretations are shown in Figures 16.0, 17.0 and 18.0.