Nema – Wiegmann WPG Series User Manual
Page 12
D ATA S U B J E C T T O C H A N G E W I T H O U T N O T I C E
E N V I R O N M E N TA L C O N T R O L S
T R I M L I N E “ N P 1 7 ” S E R I E S
S I D E - M O U N T E D A I R C O N D I T I O N E R S
K12
Standard Features
• Built-in Condensate Evaporator
• CFC-Free Refrigerant
• EMI/RFI Suppressor
• Low Temperature Control Thermostat
• M/TAB Mounting System
• NEMA 12 Rating Maintained (UL50)
‡
• UL/CUL Listed
• Gray Powder Finish
Accessories and Options
• Cooling Effect Detector
www.hubbell-wiegmann.com
Data Subject To Change Without Notice
NEMA
TYPE 12
MAINTAINED
12.13
[308.1]
17.50
[444.5]
9.00
[228.6]
1
2
3
4
12.25
[311.2]
M/TAB
THERMOSTAT
ADJUSTMENT
ACCESS
80
70
90
100
110
120
130
1500
2000
2500
3000
3500
4000
1000
500
0
Ambient Temperature (ºF)
C
ooling
C
apacit
y
(BTU/H)
Maximum enclosure
air temperature ºF
75
80
90
100
110
120
125
KA4C2.0NP17L
• Filter Recoating Adhesive
• Filters for replacement
• Internal corrosion protection
• Lifting Eyes
• Low Ambient Kit
• Short Cycle Protector
• Special materials or finishes
• Special motors, line cords, or
connectors
• Stainless or Aluminum Cabinet
• Weather Protection Kit
MODEL
RATED CAPACITY
95/95 RATING
AMBIENT TEMP. °F
VOLTS
HZ
RUNNING
APPROX.
(BTU/H)
(BTU/H)
MAX./MIN.
AMPS
WEIGHT (LBS.)
WA 4 C 2 0 N P 1 7 L
2 0 0 0
1420
1 2 5 / 5 0
1 1 5 / 1 0 0
6 0 / 5 0
6 . 7 / 6 . 5
5 9
W 2 A 4 C 2 0 N P 1 7 L
2 0 0 0
1 4 2 0
1 2 5 / 5 0
2 3 0 / 2 0 0
60/50
4.3
59
T R I M L I N E S E R I E S N P 1 7 A I R - C O O L E D PA N E L - M O U N T E D A I R C O N D I T I O N E R S
WA 4 C 2 . 0 N P 1 7 L
P E R F O R M A N C E C H A R T
12.13
[308.1]
FILTER
9.00
[228.6]
17.50
[444.5]
M/TAB
0.38 [9.5] O.D.
CONDENSATE DRAIN
6' [1.83M] MIN.
POWER CORD
38
8
12.25
[311.2]
0.50
[12.7]
0.50
[12.7]
TYP.
0.38
[9.5]
8.13
[206.5]
TYP.
6.13
[155.7]
11.25
[285.8]
5.00
[127.0]
4.13
[104.9]
0.38
[9.5]
5.75
[146.1]
17.50
[444.5]
0.38
[9.5]
3.13
[79.5]
0.88
[22.4]
6.38
[162.1]
(8) .312 [7.9]
DIA HOLES
(6)
1
/
4
-20 WELD NUTS
1
3
4
2
3
4
Weld nuts supplied for alternate mounting method to
maintain NEMA 12. Mounting Plans furnished on request.
MOUNTING PLAN
Operation within shaded area not
recommended.
Dimensions, inches [metric], are for reference only and subject to change.
‡
UL/CUL Recognized models are available as Listed at added cost.