E N V I R O N M E N TA L C O N T R O L S

COMPACT SERIES A I R C O O L E D

TOP-MOUNT AIR CONDITIONERS

K21

Standard Features
• Built-in Condensate Evaporator

• CFC-Free Refrigerant

• EMI/RFI Suppressor

• Low Temperature Control Thermostat

• UL/CUL Listed

• Gray Powder Finish

Accessories and Options
• Cooling Effect Detector

• Enclosure Heater

• Filter Recoating Adhesive

C O M PA C T S E R I E S A I R - C O O L E D T O P - M O U N T E D A I R C O N D I T I O N E R S

MODEL

RATED CAPACITY

95/95 RATING

AMBIENT TEMP. °F

VOLTS

HZ

RUNNING

APPROX.

(BTU/H)

(BTU/H)

MAX./MIN.

AMPS

WEIGHT (LBS.)

WA 4 C 4 H T R

4 0 0 0

2 2 0 0

1 2 5 / 5 0

1 1 5 / 1 0 0

6 0 / 5 0

1 3 . 1

8 5

W 2 A 4 C 4 H T R

4 0 0 0

2 2 0 0

1 1 5 / 5 0

2 3 0 / 2 0 0

6 0 / 5 0

5 . 9

8 5

2

3

4

1

POWER
CORD

THERMOSTAT
ADJUSTMENT

FILTER

17.00

[431.8]

10.25

[260.4]

20.00

[508.0]

DRAIN

2

4

80

70

90

100

110

120

130

2250

3000

3750

4500

5250

6000

1500

750

0

Ambient Temperature (ºF)

C

ooling

C

apacit

y

(B

TU

/H)

Maximum enclosure

air temperature ºF

75

80

90

100

110

120

125

KA4C4HTL

• Filters for replacement

• Internal corrosion protection

• Lifting Eyes

• Low Airflow Detector

• Low Ambient Kit

• Short Cycle Protector

• Special materials or finishes

• Special motors, linecords or

protectors

• Stainless or Aluminum Cabinet

Operation within shaded areas not
recommended.

P E R F O R M A N C E C H A R T

WA 4 C 4 H T L

(4) .25 [6.3]
WELD NUTS

10.50

[266.7]

2.50

[63.5]

13.50

[342.9]

15.50

[393.7]

17.00

[431.8]

0.75

[19.1]

1.75

[44.5]

7.75

[196.9]

5.75

[146.1]

4.00

[101.6]

2.00

[50.8]

1.75

[44.5]

4.50

[114.3]

TYP.

4.50

[114.3]

20.00

[508.0]

3

4

4

1.75

[44.5]

2.00

[50.8]

5.00

[127.0]

4.50

[114.3]

4.50

[114.3]

17.00

[431.8]

2

12.63

[320.7]

2.19

[55.6]

0.50

[12.7]

TYP.

1.50

[38.1]

8.00

[203.2]

20.00

[508.0]

10.25

[260.4]

5' [1.52] CONDENSATE
DRAIN TUBE

POWER
CORD

POWER
CORD

1

MOUNTING PLAN

www.hubbell-wiegmann.com

Data Subject To Change Without Notice