Proface AGP3500 - 10.4 DIO HMI" User Manual

Page 7

Advertising
background image

7

• The GP3000H direct connect cable’s serial interface is not isolated. When the host

(PLC) unit is also not isolated, and to reduce the risk of damaging the RS232C/
RS422/RS485 circuit, be sure to connect the SG (Signal Ground) terminal.

• If isolation is required, use the Pro-face’s RS232C isolation unit (CA3-ISO232-01), and the

following recommended equipment.

„ Ethernet Interface

Ethernet (IEEE802.3u, 10BASE-T/100BASE-TX) with modular jack connector (RJ-45)

Brown/White 2 SD(TXD)

Send Data

SDA

Send Data A(+)

Brown/White 4 ER(DTR)

Data Terminal Ready

ERA

Data Terminal Ready A(+)

Brown/None

SG

Signal Ground

SG

Signal Ground

Brown/Black 3 DR(DSR)

Data Set Ready

CSB

Clear to Send B(-)

Brown/Black 2 RS(RTS)

Request to Send

SDB

Send Data B(-)

Brown/White 3 CS(CTS)

Clear to Send

CSA

Clear to Send A(+)

Brown/Black 4 CI(RI)/VCC

Called status display/
+5 V±5% Output 0.25 A

*2

ERB

Data Terminal Ready B(-)

Green/None

FG

*3

Frame Ground
(Common with SG)

FG

*2

Frame Ground
(Common with SG)

*1 Communication method is switched via software.

*2 The RI/VCC selection is switched via software. The VCC output is not protected against

overcurrent. To prevent damage or unit malfunctions, use only the rated current.

*3 Select AWG22 cable to use out of two green cables.

Recommended Intermediate Connector

XM2A-0901 <made by OMRON Corp.>

Recommended Fastener 1

XM2Z-0003 <made by OMRON Corp.>

Recommended Cable Cover

XM2S-0913 <made by OMRON Corp.>

Cable Color

Signal Name

Direction

Description

Blue

TX +

Output

Ethernet Send (+)

White

TX -

Output

Ethernet Send (-)

Brown

RX +

Input

Ethernet Receive (+)

Gray

RX -

Input

Ethernet Receive (-)

Cable Color/

Marking Color,

Number

RS232C

*1

RS422/RS485

*1

Signal

Name

Description

Signal

Name

Description

Advertising