Marine Certification Connection

If the product is used in an environment requiring marine certification, a noise filter

must be in the power line.The noise filter must be ordered in addition to the product

using the reference PFXZFTPNDC1.

Possible Connections

Connection to a Floating (Ungrounded) DC Power System:

Some specific applications require the use of a floating (ungrounded) power system.
The characteristics of such as system, are as follows:

z

The 0 Vdc power line and Functional Ground (FG) are connected internally.

z

The 24 Vdc power line is isolated from the FG and from the outputs. The dielectric
strength for these are:

z

Primary/Secondary: 1000 Vac

z

Primary/Ground: 1000 Vac

Connection to a Ground-Referenced DC Power System:

Q : Main Power Contact
KM : Line contacts
(1) : Residual Current Detector for detecting grounding faults
(2) : PS-B unit

+

-

-

+

-

+

-

+

Low voltage

AC network

Battery

charger

Battery

Isolation

controller

Floating 24 Vdc network

- 0 Vdc

+ 24 Vdc

PS-B unit

100 - 240 Vac network

L

N

G

Q

KM

+ 24 Vdc

- +

1

1

2

+

-

PS-B unit