Danger – Proface PS4800 - 19 Panel PC" User Manual

Page 73

Advertising
background image

Main Power Connection

73

2. Associated Non-incendive Field Wiring Apparatus shall satisfy the following:

3. If the electrical parameters of the cable are unknown, the following values may
be used:

z

C

cable

= 196.85 pF/m (60 pF/ft)

z

L

cable

= 0.656

µH/m (0.20 µH/ft).

4. Wiring methods must be in accordance with the electrical code of the country in
use.

The PS-B unit must be installed in an enclosure. If installed in a Class I, Division 2
Location, the enclosure must be capable of accepting one or more Division 2 wiring
methods.

The PS-B unit is suitable for use in Class I, Division 2, Groups A, B, C, D and
provides non-incendive field wiring to apparatus in Class I, Division 2, Groups A, B,
C, D.

PS-B Unit

-

Associated Non-incendive Field
Wiring Apparatus (Mouse,
Keyboard)

V

oc

I

sc

C

a

L

a




V

max

I

max

C

i

+ C

cable

L

i

+ L

cable

DANGER

EXPLOSION HAZARD

z

Substitution of components may impair suitability for Division 2
hazardous(classified) locations.

z

Do not energize or disconnect the device while area is known to be hazardous.

z

The associated non-incendive field wiring apparatus shall not be connected in
parallel unless permitted by the associated non-incendive apparatus approval.

Failure to follow these instructions will result in death or serious injury.