14 ANASOFT User’s Guide

Start Up

Start Up Sequence

•

The program checks the computer system hardware, the access to

the system disk files, and the presence of the software key.

•

The program verifies communications to the controllers in the sys-

tem and the version of the controllers.

•

Job Directory screen appears.

•

The program prompts for the job to run. ANASOFT program is sup-

plied with a job named DEFAULT which contains all default con-
trol parameters and sets all control outputs off. When starting the
first time, enter the job name DEFAULT.

•

For systems with 8LS, 12LS, CLS, or MLS controllers, the program

prompts whether to download parameters to the controllers or
upload parameters from the controllers. When SYSTEM 32 con-
trollers are in the system, it automatically downloads.

WARNING

When controllers are in control of a process,
upload to install parameters into the ANASOFT
operating program. Downloading will install fac-
tory default values that will shut down the control
of the process. For Initial testing in the Edit mode,
enter Download.

•

After the downloading sequence is complete, the program displays

the Overview screen. If there is a problem in the program start up,
see start up errors in this section.