Alarm parameters and controller information – Watlow ANASOFT User Manual

Page 43

Advertising
background image

Loop Setup

ANASOFT User’s Guide 33

Alarm parameters and controller information

The diagram below shows the different alarm types.

The text you see on the Alarm
screen (F5). It’s the user
selected massage for alarms.

Alarm deadband. Applies to
the high process, low pro-
cess, high deviation, and low
deviation. Use it to avoid
repeated or nuisance alarms
as the PV cycles slightly

Delays all the alarms until the
alarm condition exists longer
than the delay time you set.

Controller information

Alarm digital output. Can be set for
high process, low process, high
deviation alarm, and low deviation
alarm. You can set these parameters
to one of three options:

The high and low values for your
high and low process alarms.

The spread from setpoint for your
high and low deviation alarms.

High Alarm Limit

Setpoint

Low Alarm Limit

SP + Deviation

SP - Deviation

}

Deadband

}

Deadband

}

Deadband

}

Deadband

High deviation alarm on

High deviation alarm off

Low deviation alarm on

Low deviation alarm off

High process alarm off

High process alarm on

Low process alarm on

Low process alarm off