Watlow EZ-ZONE

®

PM PID Controller

109

Appendix

Indication

Description

Possible Causes

Corrective Action

[LP;o1]

Loop Open Error

Open Loop Detect is active and

the process value did not devi-

ate by a user-selected value in

a user specified period.

• Setting of Open Loop Detect

Time incorrect

• Setting of Open Loop Detect

Deviation incorrect

• Thermal loop is open

• Open Loop Detect function not

required but activated

• Set correct Open Loop Detect

Time for application

• Set correct Open Loop Devia-

tion value for application

• Determine cause of open ther-

mal loop: misplaced sensors,

load failure, loss of power to

load, etc.

• Deactivate Open Loop Detect

feature

[LP;r1]

Loop Reversed Error

Open Loop Detect is active and

the process value is headed

in the wrong direction when

the output is activated based

on deviation value and user-

selected value.

• Setting of Open Loop Detect

Time incorrect

• Setting of Open Loop Detect

Deviation incorrect

• Output programmed for incor-

rect function

• Thermocouple sensor wired in

reverse polarity

• Set correct Open Loop Detect

Time for application

• Set correct Open Loop Devia-

tion value for application

• Set output function correctly

• Wire thermocouple correctly,

(red wire is negative)

[`rP1]

Ramping 1

Controller is ramping to new set

point

• Ramping feature is activated • Disable ramping feature if not

required

[tUN1]

Autotuning 1

Controller is autotuning the con-

trol loop

• User started the autotune

function

• Digital input is set to start

autotune

• Wait until autotune completes

or disable autotune feature

• Set digital input to function

other than autotune, if desired

No heat/cool action

Output does not activate load

• Output function is incorrectly

set

• Control mode is incorrectly set

• Output is incorrectly wired
• Load, power or fuse is open
• Control set point is incorrect

• Incorrect controller model for

application

• Set output function correctly
• Set control mode appropriately

(Open vs Closed Loop)

• Correct output wiring
• Correct fault in system
• Set control set point in appro-

priate control mode and check

source of set point: remote, idle,

profile, closed loop, open loop

• Obtain correct controller model

for application

No Display

No display indication or LED il-

lumination

• Power to controller is off
• Fuse open
• Breaker tripped
• Safety interlock switch open
• Separate system limit control

activated

• Wiring error
• Incorrect voltage to controller

• Turn on power
• Replace fuse
• Reset breaker
• Close interlock switch
• Reset limit

• Correct wiring issue
• Apply correct voltage, check

part number

No Serial Communication

Cannot establish serial commu-

nications with the controller

• Address parameter incorrect
• Incorrect protocol selected
• Baud rate incorrect
• Parity incorrect
• Wiring error
• EIA-485 converter issue
• Incorrect computer or PLC

communications port

• Incorrect software setup

• Termination resistor may be

required

• Set unique addresses on net-

work

• Match protocol between devices
• Match baud rate between de-

vices

• Match parity between devices
• Correct wiring issue
• Check settings or replace con-

verter

• Set correct communication port

• Correct software setup to match

controller

• Place 120 Ω resistor across

EIA-485 on last controller

Troubleshooting Alarms, Errors and Control Issues (cont .)