Watlow EZ-ZONE

®

PM PID Controller

40

Chapter 5 Operations Page

Operations Page

Display

Parameter Name

Description

Range

Default Modbus Rela-

tive Address

CIP

Class

Instance

Attribute

hex (dec)

Pro-

fibus

Index

Param-

eter ID

Data

Type

&

Read/

Write

[`id;S]
[ id.S]

Control Loop (1)

Idle Set Point

Set a closed loop set point

that can be triggered by

an event state.

Low Set Point to High

Set Point (Setup

Page)

75.0°F

or

units

24.0°C

Instance 1

Map 1 Map 2

2176 2656

0x6B (107)

1

9

50

7009

float
RWES

[`h;Pb]
[ h.Pb]

Control Loop (1)

Heat Proportional Band

Set the PID proportional

band for the heat outputs.

0.001 to 9,999.000°F or

units

0.001 to 5,555.000°C

25.0°F

or

units

14.0°C

Instance 1

Map 1 Map 2

1890 2370

0x97 (151)

1

6

65

8009

float
RWES

[`h;hy]
[ h.hy]

Control Loop (1)

Heat Hysteresis

Set the control switching

hysteresis for on-off con-

trol. This determines how

far into the “on” region

the process value needs

to move before the output

turns on.

0.001 to 9,999.000°F or

units

0.001 to 5,555.000°C

3.0°F or

units

2.0°C

Instance 1

Map 1 Map 2

1900 2380

0x97 (151)

1

0xB (11)

66

8010

float
RWES

[`C;Pb]
[ C.Pb]

Control Loop (1)

Cool Proportional Band

Set the PID proportional

band for the cool outputs.

0.001 to 9,999.000°F or

units

0.001 to 5,555.000°C

25.0°F

or

units

14.0°C

Instance 1

Map 1 Map 2

1892 2372

0x97 (151)

1

7

67

8012

float
RWES

[`C;hy]
[ C.hy]

Control Loop (1)

Cool Hysteresis

Set the control switching

hysteresis for on-off con-

trol. This determines how

far into the “on” region

the process value needs

to move before the output

turns on.

0.001 to 9,999.000°F or

units

0.001 to 5,555.000°C

3.0°F or

units

2.0°C

Instance 1

Map 1 Map 2

1902 2382

0x97 (151)

1

0xC (12)

68

8013

float
RWES

[``ti]
[ ti]

Control Loop (1)

Time Integral

Set the PID integral for

the outputs.

0 to 9,999 seconds per

repeat

180 sec-

onds

per

repeat

Instance 1

Map 1 Map 2

1894 2374

0x97 (151)

1

8

69

8006

float
RWES

[``td]
[ td]

Control Loop (1)

Time Derivative

Set the PID derivative

time for the outputs.

0 to 9,999 seconds

0

seconds

Instance 1

Map 1 Map 2

1896 2376

0x97 (151)

1

9

70

8007

float
RWES

[``dB]
[ db]

Control Loop (1)

Dead Band

Set the offset to the

proportional band. With

a negative value, both

heating and cooling out-

puts are active when the

process value is near the

set point. A positive value

keeps heating and cooling

outputs from fighting each

other.

-1,000.0 to 1,000.0°F

or units

-556 to 556°C

0

Instance 1

Map 1 Map 2

1898 2378

0x97 (151)

1

0xA (10)

71

8008

float
RWES

[`o;SP]
[ o.SP]

Control Loop (1)

Open Loop Set Point

Set a fixed level of output

power when in manual

(open-loop) mode.

-100 to 100% (heat and

cool)

0 to 100% (heat only)
-100 to 0% (cool only)

0.0

Instance 1

Map 1 Map 2

2162 2642

0x6B (107)

1

2

51

7002

float
RWES

Note:
Some values will be rounded off to fit in the four-character display. Full values can be
read with other interfaces.

R: Read

W: Write

E: EE-

PROM

S: User

Set