Watlow EZ-ZONE

®

PM PID Controller

55

Chapter 6 Setup Page

Setup Page

Dis-

play

Parameter Name

Description

Range

Default

Modbus Rela-

tive

Address

CIP

Class

Instance

Attribute

hex (dec)

Pro-

fibus

Index

Param-

eter ID

Data

Type

&

Read/

Write

[`C;Ag]
[ C.Ag]

Control Loop (1)

Cool Algorithm

Set the cool control

method.

[`oFF]

Off (62)

[`Pid]

PID (71)

[on;of]

On-Off (64)

Off

Instance 1
Map 1 Map 2

1886

2366

0x97 (151)

1

4

73

8004

uint

RWES

[`C;Cr]
[ C.Cr]

Control Loop (1)

Cool Output Curve

Select a cool output

curve to change the

responsiveness of the

system.

[`oFF]

Off (62)

[`Cr;A]

Non-linear Curve

1 (214)

[`Cr;b]

Non-linear Curve

2 (215)

Off

Instance 1
Map 1 Map 2

1888

2368

0x97 (151)

1

5

- - - -

8038

uint

RWES

[`h;Pb]
[ h.Pb]

Control Loop (1)

Heat Proportional

Band

Set the PID proportional

band for the heat out-

puts.

0.001 to 9,999.000°F or

units

-1,110.555 to 5,555.000°C

25.0°F or

units

14.0°C

Instance 1

Map 1 Map 2

1890 2370

0x97

(151)

1

6

65

8009

float

RWES

[`h;hy]
[ h.hy]

Control Loop (1)

Heat Hysteresis

Set the control switch-

ing hysteresis for on-off

control. This determines

how far into the “on”

region the process value

needs to move before the

output turns on.

0.001 to 9,999.000°F or

units

0.001 to 5,555.000°C

3.0°F or

units

2.0°C

Instance 1

Map 1 Map 2

1900 2380

0x97

(151)

1

0xB (11)

66

8010

float

RWES

[`C;Pb]
[ C.Pb]

Control Loop (1)

Cool Proportional

Band

Set the PID proportional

band for the cool outputs.

0.001 to 9,999.000°F or

units

0.001 to 5,555.000°C

25.0°F or

units

14.0°C

Instance 1

Map 1 Map 2

1892 2372

0x97

(151)

1

7

67

8012

float

RWES

[`C;hy]
[ C.hy]

Control Loop (1)

Cool Hysteresis

Set the control switch-

ing hysteresis for on-off

control. This determines

how far into the “on”

region the process value

needs to move before the

output turns on.

0.001 to 9,999.000°F or

units

0.001 to 5,555.000°C

3.0°F or

units

2.0°C

Instance 1

Map 1 Map 2

1902 2382

0x97

(151)

1

0xC (12)

68

8013

float

RWES

[``ti]
[ ti]

Control Loop (1)

Time Integral

Set the PID integral for

the outputs.

0 to 9,999 seconds per

repeat

180 sec-

onds per

repeat

Instance 1

Map 1 Map 2

1894 2374

0x97

(151)

1

8

69

8006

float

RWES

[``td]
[ td]

Control Loop (1)

Time Derivative

Set the PID derivative

time for the outputs.

0 to 9,999 seconds

0

seconds

Instance 1

Map 1 Map 2

1896 2376

0x97

(151)

1

9

70

8007

float

RWES

Note:
Some values will be rounded off to fit in the four-character display. Full values can be
read with other interfaces.

R: Read

W: Write

E:

EE-

PROM

S:

User

Set