Installation, Figure 2, smartslot installation – APC SmartSlot Series User Manual
Page 5
 
2. Installation
Use the following procedure to install SmartSlot Measure-UPS II:
1.
Install and configure any software or hardware that will be used 
with Measure-UPS II for data reporting (see software and hard-
ware compatibility above).
2.
Using figure 2 as a guide, install Measure-UPS II in the host 
SmartSlot. Use a #2 Phillips head screwdriver to remove the host 
device SmartSlot cover plate. Install Measure-UPS II. Replace the 
cover plate screws. Note: Measure-UPS II is sensitive to static 
electricity. Handle Measure-UPS II by the end plate only. Do not 
touch the exposed printed circuit board. While it is not possible to 
install Measure-UPS II upside down, it is possible to damage it in 
the attempt. Note that the edges of the printed circuit board align 
with the locating slots in the sides of the SmartSlot. The Smart-
Slot may be oriented horizontally or vertically in the host device. 
The host device may be on or off during installation.
3.
Connect the supplied probe to probe connector 1 on Measure-
UPS II. Note: probe connector 2 is not used in Measure-UPS II.
4.
Place the probe where desired using the supplied hook and loop 
fasteners, if needed. Note: The Measure-UPS II probe is designed 
for use in a controlled environment. Place it in an area that is 
within the environment limits set in the specifications (see section 
9.) The location must be free from direct sunlight, excessive 
moisture, and dust.
Figure 2, SmartSlot installation